UPS5000-S-(35 kVA-210 kVA)
User Manual (Singapore, 35 kVA Power Modules)
Figure 5-22 Logs
----End
5.7 Transferring to Maintenance Bypass Mode
Context
Installing a lock on the maintenance bypass switch is advised. The lock core has a
diameter of 5–10 mm.
Strictly observe the following procedure to transfer the UPS to maintenance bypass mode.
Otherwise, loads may power off.
In maintenance bypass mode, the mains supplies power to the loads directly over the
maintenance bypass. If the mains is not normal, the loads may power off.
Procedure
Step 1 Transfer the UPS to the bypass mode.
Step 2 Turn on the maintenance bypass switch by rotating the handle clockwise 90 degrees so that
the handle points leftwards.