Huawei UPS5000-S Series User Manual page 123

Hide thumbs Also See for UPS5000-S Series:
Table of Contents

Advertisement

UPS5000-S-(35 kVA-210 kVA)
User Manual (Singapore, 35 kVA Power Modules)
Item
D.G. ECO
Bypass Supply
RAM
verification
Record time
after fault
Collect real-
time site
waveform
Input Settings
Item
Input
adaptability
Issue 02 (2020-01-10)
All manuals and user guides at all-guides.com
Description
Indicates whether ECO bypass is
allowed to supply power in D.G.
mode. When the D.G. is
connected to the dry contact
signal GEN:
If this parameter is set to
Enable, the system can enter
ECO bypass mode when the
D.G. supplies power to the
bypass and the ECO function
is enabled.
If this parameter is set to
Disable, the system is not
allowed to enter ECO mode
when the D.G. supplies power
to the bypass.
Enable or disable the memory
check function. If this parameter
is set to Enable, the control chip
RAM working status is checked
regularly. If this parameter is set
to Disable, regular check is
disabled.
Indicates the time for storing
fault data after the UPS
experiences a fault. The default
value is 0 ms, which means that
the data during 20 ms before the
fault occurs is recorded. If the
value is set to 40 ms, it means
that the data during 20 ms before
the fault occurs and the data
during 40 ms after the fault
occurs are recorded, and the like.
If this parameter is set to Enable,
one waveform can be stored
manually.
Description
The value of Input adaptability
can be Strong or Weak. Strong
input adaptability applies to the
D.G. or input sources whose
input current has high frequency
oscillation. In this mode, the total
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Enable
Disable, Enable
Disable
Disable, Enable
0 ms
0 ms, 20 ms, 40
ms, 60 ms, 80
ms
Disable
Disable, Enable
Default Value
Value Range
Strong
Strong, Weak
115