Huawei UPS5000-S Series User Manual page 56

Hide thumbs Also See for UPS5000-S Series:
Table of Contents

Advertisement

UPS5000-S-(35 kVA-210 kVA)
User Manual (Singapore, 35 kVA Power Modules)
Table 3-2 Recommended cross-sectional areas for power cables
Item
Mains
Mains input current
input
(A)
Recommended
cross-sectional
2
area (mm
)
Bypass
Bypass input current
input
(A)
Recommended
cross-sectional
2
area (mm
)
Output
Output current (A)
Recommended
cross-sectional
2
area (mm
)
Batter
Battery nominal
y input
discharge current (A)
Battery maximum
discharge current (A)
Recommended
cross-sectional
2
area (mm
)
When selecting, connecting, and routing power cables, follow local safety regulations
and rules.
When the external conditions change, for example, the cable layout or ambient
temperatures, perform verification in accordance with the IEC-60364-5-52 or the local
regulations.
Issue 02 (2020-01-10)
All manuals and user guides at all-guides.com
35 kVA
70 kVA
91
164
L1
4x25
4x50
L2
L3
N
PE
25
25
54
107
L1
4x25
4x50
L2
L3
N
PE
25
25
54
107
U
4x25
4x25
V
W
N
PE
25
25
81
162
93
185
+
2x25
2x35
-
PE
25
25
Copyright © Huawei Technologies Co., Ltd.
105 kVA
140 kVA
238
311
4x95
4x120
50
70
228
304
4x95
4x120
50
70
160
213
4x50
4x95
25
50
243
324
278
370
2x70
2x95
35
50
3 Installation
175 kVA
210 kVA
385
458
4x150
2x(4x95)
70
95
380
456
4x150
2x(4x95)
70
95
266
320
4x120
4x150
70
70
404
485
462
555
2x150
2x185
70
95
48