UPS5000-S-(35 kVA-210 kVA)
User Manual (Singapore, 35 kVA Power Modules)
Item
Maintenance
period (d)
Chg. cur.
limiting coef.
(C10)
Cell float
voltage (V/cell)
Cell equalized
volt. (V/cell)
Dis. cur. 0.1C
EOD (V/cell)
Dis. cur. 0.3C
EOD (V/cell)
Dis. cur. 0.5C
EOD (V/cell)
Dis. cur. 1.0C
EOD (V/cell)
Sched. shallow
dis. test
Shallow dis.
test dis. ratio
(%)
Dry Contact Settings
Set only the dry contacts that are needed. Otherwise, the UPS may not run properly.
When a dry contact card is disabled, its dry contact signals are disabled.
After a dry contact card is enabled, its dry contact signals can be displayed on the LCD.
Disable all the dry contacts for a dry contact card that is not connected and all the dry
contacts that are not used to prevent false alarms.
( ) encloses a unit, and [ ] encloses silk screen.
Issue 02 (2020-01-10)
All manuals and user guides at all-guides.com
Description
the installation time) comes.
Specifies the interval for
reminding users of battery
maintenance.
The charging current limit is a
multiple of the battery capacity.
Specifies the battery float
charging voltage.
Specifies the battery equalized
charging voltage.
Specifies the EOD threshold
when the discharging current is
0.1C, 0.3C, 0.5C, and 1.0C
respectively.
When certain conditions are met,
the charger shuts down, and
batteries supply power to loads.
The system records the battery
discharge data as the reference
for battery capacity and lifespan.
Set the proportion of the
discharge capacity to the total
discharge capacity. The value is
configurable in any mode.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
0
0–365
0.1C10
0.05C10 to
0.15C10
2.25 V/cell
2.23 V/cell to
2.30 V/cell
2.35 V/cell
2.30 V/cell to
2.40 V/cell
1.80 V/cell
1.8–1.9
1.80 V/cell
1.8–1.9
1.75 V/cell
1.75–1.85
1.60 V/cell
1.6–1.75
Disable
Disable, Enable
20%
10%–50%
98