Huawei UPS5000-S Series User Manual page 193

Hide thumbs Also See for UPS5000-S Series:
Table of Contents

Advertisement

UPS5000-S-(35 kVA-210 kVA)
User Manual (Singapore, 35 kVA Power Modules)
Alarm ID
Alarm Name Severity
(Alarm ID-
Cause ID)
0006-1
Mains
undervoltage
0010-1
Abnormal
bypass
voltage
0010-2
0011-1
Bypass phase
reversed
0012-1
Bypass
neutral absent
0020-1
Battery
connected
reversely
0021-1
Battery EOD
Issue 02 (2020-01-10)
All manuals and user guides at all-guides.com
Cause
Minor
The mains is not
normal.
The power
module sampling
circuit is not
normal.
Minor
The bypass
voltage range is
not correctly set.
The bypass input
voltage is not
normal.
The bypass
frequency range
is not correctly
set.
The bypass input
frequency is not
normal.
Minor
The phase sequence
of the three-phase
bypass input is
reversed.
Minor
The neutral wire of
bypass input is not
installed properly.
Critical
Batteries are not
properly installed.
Critical
The battery voltage
reaches the EOD
voltage threshold due
to continuous
Copyright © Huawei Technologies Co., Ltd.
Solution
2. Check that the neutral wire to the
power distribution system is
normal.
Check whether the mains voltage
ranges from 80 V (excluding 80 V) to
176 V. If no, the mains monitoring
circuit for the power module is faulty.
Replace the faulty module.
1. Check the bypass input voltage or
cable connections with a
multimeter.
2. Check the voltage system and
bypass voltage thresholds
configured on the LCD.
1. Check the bypass input voltage or
cable connections with a
multimeter.
2. Check the bypass input frequency.
Check the rated frequency and
frequency range configured on the
LCD.
Check whether the cable phase
sequence is correct using a
multimeter. If no multimeter is
available, exchange the positions of
any two cables.
1. Secure or connect the neutral wire
to the cabinet if it is loose or
disconnected.
2. Check that the neutral wire to the
power distribution system is
normal.
1. Check whether battery polarities
are correctly installed by using a
multimeter. If no, correct the
installation.
2. Check whether the battery input
voltage of the UPS is normal. If
yes, the battery sampling circuit of
the power module is faulty.
Replace the power module.
If the BCB box is configured, check
whether the BCB box trips. If it trips,
close the BCB box switch.
C Alarm List