Huawei UPS5000-S Series User Manual page 199

Hide thumbs Also See for UPS5000-S Series:
Table of Contents

Advertisement

UPS5000-S-(35 kVA-210 kVA)
User Manual (Singapore, 35 kVA Power Modules)
Alarm ID
Alarm Name Severity
(Alarm ID-
Cause ID)
0337
PDC bypass
input breaker
open
0338
PDC output
breaker open
0341
PDC Maint.
breaker closed
0342
Mains input
breaker open
0343
BPM input
breaker open
0340
Maint.
breaker closed
0335
Generator
connected
0594-1
Insufficient
redundant
racks
0095-1
Insuffi.
redundancy
0096-1
ECO volt.
Abnormal
Issue 02 (2020-01-10)
All manuals and user guides at all-guides.com
Cause
Critical
The bypass input
circuit breaker on the
PDC is OFF.
Critical
The output circuit
breaker on the PDC
is OFF.
Minor
The maintenance
circuit breaker on the
PDC is ON.
Critical
The mains input
circuit breaker is
OFF.
Critical
The bypass input
circuit breaker is
OFF.
Minor
The maintenance
circuit breaker is
ON.
Warning
The generator is
connected.
Minor
The load is
excessive.
The configured
number of
redundant racks is
incorrect.
Minor
The load is
excessive.
The configured
number of
redundant
modules is
incorrect.
Minor
The ECO bypass
voltage or
frequency is out
of the preset
range.
Copyright © Huawei Technologies Co., Ltd.
Solution
alarms.
The running status is displayed. No
further measures are required.
1. Check that all UPS output circuit
breakers are ON.
2. On the LCD, check that PDC
output breaker open alarm has
disappeared. If the alarm persists,
tap the Clear Fault button to clear
the alarm.
The running status is displayed. No
further measures are required.
The running status is displayed. No
further measures are required.
The running status is displayed. No
further measures are required.
The running status is displayed. No
further measures are required.
The running status is displayed. No
further measures are required.
1. Reduce the load.
2. Decrease the configured number of
redundant racks.
1. Reduce the load.
2. Decrease the configured number of
redundant modules.
1. Check the bypass input voltage
and frequency.
2. Check that the rated voltage, rated
frequency, ECO bypass voltage
C Alarm List
191