UPS5000-S-(35 kVA-210 kVA)
User Manual (Singapore, 35 kVA Power Modules)
Indicator
Alarm
indicator
Fault indicator
Functions
The power module consists of a power factor correction (PFC) rectifier, inverter, and DC/DC
converter. The power module performs AC/DC or DC/DC conversion on the mains and
battery inputs, and stabilizes the bus voltage. The inverter (DC/AC) converts the inputs into
sine wave outputs.
Specifications
Dimensions (H x W x D): 130 mm x 442 mm x 620 mm
Weight: ≤ 35 kg
Rated output capacity: 35 kVA/35 kW
Issue 02 (2020-01-10)
All manuals and user guides at all-guides.com
Color
Status
Off
Yellow
Steady on
Off
Red
Steady on
Off
Copyright © Huawei Technologies Co., Ltd.
Description
Hz, on for 0.125s and off for 0.125s).
The rectifier CPLD software is being
upgraded.
A minor alarm is generated for the
inverter or rectifier.
There is no minor alarm for the inverter
or rectifier, or the rectifier CPLD
software is being upgraded.
A critical alarm is generated for the
inverter or rectifier.
There is no critical alarm for the inverter
or rectifier, or the rectifier CPLD
software is being upgraded.