Huawei UPS5000-S Series User Manual page 151

Hide thumbs Also See for UPS5000-S Series:
Table of Contents

Advertisement

UPS5000-S-(35 kVA-210 kVA)
User Manual (Singapore, 35 kVA Power Modules)
Figure 5-1 Settings Wizard
Set the time and date correctly. Incorrect time and date will cause false fault analysis during
maintenance or repair.
After you set network parameters, connect the UPS to the network over a network cable, which
enables you to remotely manage the UPS. If you do not need remote management, retain the default
network parameter settings.
Step 2 After you set parameters on the Settings Wizard screen, the MDU displays the Bypass mode
and No battery alarms, which do not need to be handled. If there is any other alarm, you need
to rectify the fault.
After you set parameters on the Settings Wizard screen, choose System Info > Settings >
Advanced Param. Check that Requisite modules and Redundant modules match the actual
values.
If dry contact signals are connected to the system, choose System Info > Settings > Dry contacts
and check that the connected dry contacts have been enabled and that the disconnected dry contacts
have been disabled.
Step 3 View the system running diagram on the MDU to check that the UPS is working in bypass
mode.
----End
Issue 02 (2020-01-10)
All manuals and user guides at all-guides.com
Copyright © Huawei Technologies Co., Ltd.
5 Operations
143