Huawei UPS5000-S Series User Manual page 101

Hide thumbs Also See for UPS5000-S Series:
Table of Contents

Advertisement

UPS5000-S-(35 kVA-210 kVA)
User Manual (Singapore, 35 kVA Power Modules)
Item
NTC
Input Settings
Figure 4-23 Input settings
Item
D.G. mode
D.G. power
limiting (kVA)
D.G. charger
power ratio (%)
Input cur.
limiting
Issue 02 (2020-01-10)
All manuals and user guides at all-guides.com
Description
module start delay (s) is 5.0.
The start delay of a module in a
rack varies depending on the rack
number and module number. #1
module in rack 1 does not have a
start delay.
The short-distance battery
temperature sensor monitors the
ambient temperature near
batteries, and ensures that
batteries work reliably and
securely.
Description
Set this parameter to Enable
when a D.G. connects to the
input PDC. The UPS enters the
D.G. mode when a D.G. is
detected over dry contacts.
Set these two parameters to
control the valid input current
and limiting input current, which
prevents load impact and
facilitates better cooperation
between the UPS and the D.G.
Specifies whether to enable or
disable input current limiting to
protect generators.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Disable
Disable, Enable
Default Value
Value Range
Disable
Disable, Enable
Depends on the
0 kVA to 5000
actual model.
kVA
0
0%–100%
Disable
Disable, Enable
93