UPS5000-S-(35 kVA-210 kVA)
User Manual (Singapore, 35 kVA Power Modules)
Item
Output freq.
track rate
(Hz/s)
Bypass Settings
Figure 4-25 Bypass settings
Item
Maximum
bypass voltage
Minimum
Issue 02 (2020-01-10)
All manuals and user guides at all-guides.com
Description
This parameter can be adjusted
based on site requirements. If
Output freq. track rate (Hz/s)
is slow, the inverter frequency is
different from the bypass
frequency when the bypass
frequency changes. If output is
overloaded or the inverter is
faulty, an interruption (less than
20 ms) occurs when the UPS
transfers from normal mode to
bypass mode. If Output freq.
track rate (Hz/s) is fast, the
inverter frequency is unstable.
Description
When the difference between the
bypass voltage and the rated
voltage exceeds the upper
threshold for the bypass voltage,
the system determines that the
bypass voltage is not normal and
that the bypass is unavailable.
When the difference between the
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
0.6 Hz/s
0.1 Hz/s to 2.0
Hz/s
Default Value
Value Range
When the voltage level is 380 V,
the value range is +10%, +15%,
+20%, and +25%. The default
value is +15%.
When the voltage level is 400 V,
the value range is +10%, +15%,
and +20%. The default value is
+15%.
When the voltage level is 415 V,
the value range is +10% and
+15%. The default value is
+10%.
–20%
–10%, –15%, –
95