Usb Port; Rs-232 Port; Sdi-12 Ports; General Serial Communications - Campbell CR300 Series Operator's Manual

Hide thumbs Also See for CR300 Series:
Table of Contents

Advertisement

6.5.1.1 USB Port

One micro-B USB port, labeled USB, for communicating with a PC through
datalogger support software. Powering through the USB port has the limitations
discussed in Section 6.7.1.1, Power Sources

6.5.1.2 RS-232 Port

One nine-pin DCE port, labeled RS-232, normally used to communicate with a
PC running datalogger support software, to connect a modem read a smart
sensor (see Section 6.5.2, General Serial Communications
modem adapter attached, it serves as a DTE device.

6.5.1.3 SDI-12 Ports

SDI-12 is a 1200-baud protocol that supports many smart sensors (see Section

6.5.3, SDI-12 Communications

SDI-12 communication port.

6.5.2 General Serial Communications

The CR300 supports two-way serial communication through two ports
configurable for RS-232 input. In addition to the nine-pin RS-232 port,
terminals C1 and C2 can be configured as a pair to create an RS-232
communication port, called Com1. Ports can be formatted as described in
CRBasic Editor Help.
These two ports can be used with smart sensors that deliver measurement data
through serial data protocols or with devices such as modems that
communicate using serial data protocols.
CRBasic instructions for general serial communications include:
To communicate over a serial port, it is important to be familiar with the
protocol of the sensor or device. Refer to the manual of the sensor or device to
find its protocol and then select the appropriate options for each CRBasic
parameter. See the application note
Scientific
programming details and examples.
6.5.3 SDI-12 Communications
SDI-12 is a smart-sensor protocol that uses one terminal configured for SDI-
12. Terminals C1 and C2 can each be configured as an SDI-12 communication
terminal.
Modbus
DNP3
Campbell Scientific PakBus networks
(p. 35)
SerialOpen()
SerialClose()
SerialIn()
SerialInRecord()
SerialInBlock()
SerialOut()
SerialOutBlock()
Dataloggers, available at www.campbellsci.com, for more
CR300-Series Datalogger
.
(p. 39)
). With a null
(p. 35)
). C1 and C2 can each be configured as an
Interfacing Serial Sensors with Campbell
35

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cr300-rf407Cr300-rf412Cr300-rf422

Table of Contents