Hitachi Relion 650 Series Technical Manual page 292

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 12
Monitoring
AuxPosAvail
Electrical
able
feedback
signal open
Status
NC
Not Healthy
Healthy
NO and NC
Not Healthy
Healthy
Case No 3
None
X
NO
X
X
NC
X
X
NO and NC
X
X
X
X
CBSTSCFLX represents a consolidated CB status, derived from available electrical and mechanical
feedback signals.
286
Electrical
INPNOLX
feedback
signal open
Status
Not Healthy
X
X
Healthy
X
X
Not Healthy
0
0
1
1
Healthy
0
0
1
1
X
X
X
0
X
1
X
X
X
X
X
0
X
0
X
1
X
1
© 2021 Hitachi Energy. All rights reserved.
INPNCLX
CBSTSLX
0
El open mec
close (6)
1
El open mec
open (5)
0
El close
mec close
(10)
1
El close
mec open
(9)
0
El open mec
inv (4)
1
El open mec
open (5)
0
El open mec
close (6)
1
El open mec
faulty (7)
0
El close
mec inv (8)
1
El close
mec open
(9)
0
El close
mec close
(10)
1
El close
mec faulty
(11)
X
El inv mec
inv (0)
X
El inv mec
open (1)
X
El inv mec
close (2)
0
El inv mec
close (2)
1
El inv mec
open (1)
0
El inv mec
inv (0)
1
El inv mec
open (1)
0
El inv mec
close (2)
1
El inv mec
faulty (3)
1MRK 511 557-UEN Rev. A
CBSTNLLX
CBSTNCLX
1
0
0
1
1
0
0
1
0
1
0
1
1
0
1
1
1
0
0
1
1
0
1
1
0
0
0
1
1
0
1
0
0
1
0
0
0
1
1
0
1
1
Technical Manual
CBSTSCFLX
Unknown
(0)
Open (1)
Closed (2)
Unknown
(0)
Unknown
(0)
Open (1)
Unknown
(0)
Unknown
(0)
Unknown
(0)
Unknown
(0)
Closed (2)
Unknown
(0)
Unknown
(0)
Open (1)
Closed (2)
Closed (2)
Open (1)
Unknown
(0)
Open (1)
Closed (2)
Unknown
(0)

Hide quick links: