Signals; Settings; Operation Principle - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 557-UEN Rev. A
13.4.4

Signals

Table 315: GOOSEINTRCV Input signals
Name
BLOCK
Table 316: GOOSEINTRCV Output signals
Name
INTOUT
DATAVALID
COMMVALID
TEST
13.4.5

Settings

Table 317: GOOSEINTRCV Non group settings (basic)
Name
Values (Range)
Operation
13.4.6

Operation principle

The DATAVALID output will be 1 (high) as long as the incoming message contains valid data. In case
of invalid data INTOUT will be forced to 0.
The COMMVALID output will become 0 (low) when the subscribed GOOSE messages are not
received as expected. In this case INTOUT will retain the last valid value.
The TEST output will go HIGH if the sending IED is in test mode.
Technical Manual
Type
BOOLEAN
Type
INTEGER
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Off
-
On
The input of this GOOSE block must be linked in SMT to receive the integer values.
The implementation for IEC 61850 quality data handling is restricted to a simple
level. If quality data validity is GOOD then the DATAVALID output will be HIGH. If
quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
© 2021 Hitachi Energy. All rights reserved.
Default
Description
0
Block of function
Description
Integer output
Data valid for integer output
Communication valid for integer output
Test output
Step
Default
-
Off
Station communication
D0E7511T201305151403 v1
D0E7512T201305151403 v1
D0E7513T201305151403 v1
Description
Operation Off/On
D0E7463T201305151403 v1
Section 13