1MRK 511 557-UEN Rev. A
13.5.6

Operation principle

The DATAVALID output will be 1 (high) as long as the incoming message contains valid data. In case
of invalid data MVOUT will be forced to 0.
The COMMVALID output will become 0 (low) when the subscribed GOOSE messages are not
received as expected. In this case MVOUT will retain the last valid value.
The TEST output will go HIGH if the sending IED is in test mode.
13.6
GOOSE function block to receive a single point value
GOOSESPRCV
13.6.1

Identification

Function description
GOOSE function block to receive a
single point value
13.6.2

Functionality

GOOSESPRCV is used to receive a single point value using IEC 61850 protocol via GOOSE.
13.6.3

Function block

BLOCK
D0E13786T201305151403 V1 EN-US
Figure 157: GOOSESPRCV function block
13.6.4

Signals

Table 321: GOOSESPRCV Input signals
Name
BLOCK
Technical Manual
The input of this GOOSE block must be linked in SMT to receive the measurand
values.
The implementation for IEC 61850 quality data handling is restricted to a simple
level. If quality data validity is GOOD then the DATAVALID output will be HIGH. If
quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW
GOOSESPRCV
^SPOUT
DATAVALID
COMMVALID
TEST
IEC10000248-1-en.vsd
Type
BOOLEAN
© 2021 Hitachi Energy. All rights reserved.
IEC 61850
IEC 60617
identification
identification
GOOSESPRCV
-
Default
Description
0
Block of function
Section 13
Station communication
D0E7464T201305151403 v1
D0E7517T201305151403 v1
ANSI/IEEE C37.2
device number
-
D0E7461T201305151403 v1
D0E7456T201305151403 v1
D0E7505T201305151403 v1
353