Section 12
Monitoring
High-high limit
High limit
Low limit
Low-low limit
D0E11991T201305151403 V1 EN-US
Figure 88:
Each analogue output has one corresponding supervision level output (X_RANGE). The output
signal is an integer in the interval 0-4 (0: Normal, 1: High limit exceeded, 3: High-high limit exceeded,
2: below Low limit and 4: below Low-low limit). The output may be connected to a measurement
expander block (MVEXP) to get measurement supervision as binary signals.
The logical value of the functional output signals changes according to
The user can set the hysteresis (XLimHyst), which determines the difference between the operating
and reset value at each operating point, in wide range for each measuring channel separately. The
hysteresis is common for all operating values within one channel.
Actual value of the measured quantity
The actual value of the measured quantity is available locally and remotely. The measurement is
continuous for each measured quantity separately, but the reporting of the value to the higher levels
depends on the selected reporting mode. The following basic reporting modes are available:
Cyclic reporting (Cyclic)
Amplitude dead-band supervision (Dead band)
Integral dead-band supervision (Int deadband)
Cyclic reporting
The cyclic reporting of measured value is performed according to chosen setting (XRepTyp). The
measuring channel reports the value independent of amplitude or integral dead-band reporting.
In addition to the normal cyclic reporting the IED also report spontaneously when measured value
passes any of the defined threshold limits.
170
Y
X_RANGE=0
X_RANGE=2
X_RANGE=4
Presentation of operating limits
© 2021 Hitachi Energy. All rights reserved.
X_RANGE = 3
X_RANGE= 1
Hysteresis
X_RANGE=0
1MRK 511 557-UEN Rev. A
t
en05000657.vsd
Figure
88.
D0E6125T201305151403 v1
D0E6126T201305151403 v2
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Switchsync pwc600

Table of Contents