Monitored Data - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 557-UEN Rev. A
12.18.6

Monitored data

Table 261: ACBMSCBR Monitored data
Name
CBSTSLX
CBSTSCFLX
CBSTNCLX
CBSTNOLX
LOADONLX
LOADOFFLX
OVCURLX
UPHSFTLX
ERELORTLX
ERELOTCLX
ERELOTOLX
PARCTMLX
PPRESTRAX
PELORTLX
PELORTCLX
Table continues on next page
Technical Manual
Type
Values (Range)
INTEGER
0=El inv mec inv
1=El inv mec
open
2=El inv mec
close
3=El inv mec
faulty
4=El open mec
inv
5=El open mec
open
6=El open mec
close
7=El open mec
faulty
8=El close mec
inv
9=El close mec
open
10=El close mec
close
11=El close mec
faulty
INTEGER
0=Unknown
1=Open
2=Closed
BOOLEAN
-
BOOLEAN
-
BOOLEAN
-
BOOLEAN
-
BOOLEAN
-
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
© 2021 Hitachi Energy. All rights reserved.
Unit
Description
-
CB position derived from mechanical
and electrical status for this phase
-
CB position confirmation to SSCPOW for
this phase
-
CB open status derived from auxiliary
contacts and primary feedback signal for
this phase
-
CB closed status derived from auxiliary
contacts and primary feedback signal for
this phase
-
RMS of selected feedback signal is
above OpenCThreshold
-
RMS of selected feedback signal is
below OpenFThreshold
-
Overcurrent detected in this phase
deg
Phase shift between the connected
source and load voltage in this phase
ms
Difference between actual and predicted
electrical operation time for this phase
ms
Difference between actual and predicted
electrical making times for this phase
ms
Difference between actual and predicted
electrical interrupting times for this phase
ms
Predicted arcing time for this phase
deg
Predicted pre-strike angle for this phase
ms
Predicted electrical operation time for
this phase
ms
Predicted electrical closing (making) time
for this phase
Section 12
Monitoring
PID-7613-MONITOREDDATA v1
271

Advertisement

Table of Contents
loading

This manual is also suitable for:

Switchsync pwc600

Table of Contents