1MRK 511 557-UEN Rev. A
Setting PULSED
In this mode, pressing the function key for minimum 0.5 seconds (detection period, not changeable)
changes the output to 1 (high). After a time defined by PulseTime, the output will return to 0 (low)
irrespective of the status of the function key.
If the function key is pressed again, a new pulse will be generated only if the output is 0 at the end of
the detection period. See
Key press
Output
IEC17000250 V1 EN-US
Figure 25:
5.6.6.2

Input function

The binary input LEDCTL is active only when Type is set to 'Control'. In this mode, the status (ON/
OFF) of the yellow LED on the function key directly follows the status of LEDCTL. This functionality is
independent of the Mode setting.
Technical Manual
Figure
25.
0.5 s
PulseTime
Sequence diagram for setting PULSED
© 2021 Hitachi Energy. All rights reserved.
0.5 s
0.5 s
PulseTime
Section 5
Local HMI
PulseTime
IEC17000250-1-en.vsd
D0E5704T201305151403 v1