1MRK 511 557-UEN Rev. A
a,b,c,d,e,f,m, n = Constants (settings)
x = Input value
y = Output value
In equation mode, the WARNING output goes high when large output value numbers, typically above
8388607 (absolute), are rounded to the last decimal point.
10.1.6.4

Status information

The following table summarizes the status information generated by the ANSCAL function.
Table 64:
Name
WARNING
ALARM
SENSTSOUT
10.2

Double point input status time monitoring DPISTTIM

10.2.1

Identification

Function description
Double point input status time
monitoring
10.2.2

Functionality

The Double point indication status times DPISTTIM function computes the status times of a double
point indication (DPI) by counting the times since the last status changeovers. The inputs for this
function are two boolean signals of a DPI. The outputs provide the time either in milliseconds,
seconds, minutes, or hours from the last status changeover. DPISTTIM function can be used for
computing the idle times, that is, time since the last open and close operations of a switch.
Technical Manual
If x is large and m, n, e are not set to small values, the output will overflow. Similarly,
if x can be negative then m and n must be natural numbers.
ANSCAL status output signals
Description
Combined warning signal, TRUE (1) on any of the following conditions:
In Chart mode, when the input signal is inside the permitted range but outside the
compensation range (see
In Equation mode, if the absolute output value is too large to ensure full numerical
accuracy
Combined alarm signal, TRUE (1) if any of the following conditions is detected:
Faulty sensor
Settings X for curve point input values in Chart mode are out of sequence
INPUT value is lower than LowLimit or higher than HighLimit
BLKFUNC input is 1
Sensor status output for IEC 61850 reporting purpose:
TRUE (1) – Sensor status is unhealthy
FALSE (0) – Sensor status is healthy
IEC 61850 identification IEC 60617
DPISTTIM
© 2021 Hitachi Energy. All rights reserved.
Table
63.)
identification
-
Section 10
General calculation
GUID-F6CACBCF-9DC6-4769-9995-2BB5282D544D v1
GUID-7D43CC6A-D4C6-4812-BF8D-87E4ABED0D55 v1
GUID-26CEB250-137A-469E-9FC9-3131E79B5200 v1
ANSI/IEEE C37.2 device
number
-
GUID-69D61F41-58D4-41FC-B487-405B9F43869D v1