Run-Time Model - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 557-UEN Rev. A
Table 333: Explanations of internal signals
Name of signal
Internal Fail
Internal Warning
Real Time Clock Error
Time Synch Error
Runtime Exec Error
IEC61850 Error
SW Watchdog Error
Runtime App Error
Setting(s) Changed
Setting Group(s) Changed
Change Lock
File System Error
14.1.4.2

Run-time model

The analog signals to the A/D converter are internally distributed into two different converters, one
with low amplification and one with high amplification, see
D0E12659T201305151403 V1 EN-US
Figure 165: Simplified drawing of A/D converter for the IED.
Technical Manual
Reasons for activation
This signal will be active if one or more of the following internal signals are
active; Real Time Clock Error, Runtime App Error, Runtime Exec Error, SW
Watchdog Error, File System Error
This signal will be active if one or more of the following internal signals are
active; IEC 61850 Error, DNP3 Error
This signal will be active if there is a hardware error with the real time
clock.
This signal will be active when the source of the time synchronization is
lost, or when the time system has to make a time reset.
This signal will be active if the Runtime Engine failed to do some actions
with the application threads. The actions can be loading of settings or
parameters for components, changing of setting groups, loading or
unloading of application threads.
This signal will be active if the IEC 61850 stack did not succeed in some
actions like reading IEC 61850 configuration, startup, for example.
This signal will be activated when the IED has been under too heavy load
for at least 5 minutes. The operating systems background task is used for
the measurements.
This signal will be active if one or more of the application threads are not in
the state that Runtime Engine expects. The states can be CREATED,
INITIALIZED, RUNNING, for example.
This signal will generate an internal event to the internal event list if any
setting(s) is changed.
This signal will generate an internal event to the Internal Event List if any
setting group(s) is changed.
This signal will generate an internal Event to the Internal Event List if the
Change Lock status is changed
This signal will be active if both the working file and the backup file are
corrupted and cannot be recovered.
ADx
ADx_Low
ADx_High
© 2021 Hitachi Energy. All rights reserved.
Figure
165.
x
1
u
1
x
2
ADx
Controller
x
1
u
1
x
2
IEC05000296-3-en.vsd
Section 14
Basic IED functions
D0E7074T201305151403 v1
369

Advertisement

Table of Contents
loading

This manual is also suitable for:

Switchsync pwc600

Table of Contents