Section 14
Basic IED functions
Some signals are available from the INTERRSIG function block. The signals from INTERRSIG
function block are sent as events to the station level of the control system. The signals from the
INTERRSIG function block can also be connected to binary outputs for signalization via output relays
or they can be used as conditions for other functions if required/desired.
Individual error signals from I/O modules can be obtained from respective module in the Signal
Matrix tool. Error signals from time synchronization can be obtained from the time synchronization
block INTERRSIG.
14.1.4.1

Internal signals

SELFSUPEVLST function provides several status signals, that tells about the condition of the IED.
As they provide information about the internal status of the IED, they are also called internal signals.
The internal signals can be divided into two groups.
Standard signals are always presented in the IED, see
Hardware dependent internal signals are collected depending on the hardware configuration,
see
Explanations of internal signals are listed in
Table 331: SELFSUPEVLST standard internal signals
Name of signal
Internal Fail
Internal Warning
Real Time Clock Error
Time Synch Error
Runtime App Error
Runtime Exec Error
IEC61850 Error
SW Watchdog Error
Setting(s) Changed
Setting Group(s) Changed
Change Lock
File System Error
Table 332: Self-supervision's hardware dependent internal signals
Card
PSM
TRM
COM
BIO
PIO
368
Table
332.
Name of signal
PSM-Error
TRM-Error
COM-Error
BIO-Error
PIO-Error
© 2021 Hitachi Energy. All rights reserved.
Table
331.
Table
333.
Description
Internal fail status
Internal warning status
Real time clock status
Time synchronization status
Runtime application error status
Runtime execution error status
IEC 61850 error status
SW watchdog error status
Setting(s) changed
Setting group(s) changed
Change lock status
Fault tolerant file system status
Description
Power supply module error status
Transformator module error status
Communication module error status
Binary input/output module error status
Precision binary input/output module error status
1MRK 511 557-UEN Rev. A