Goose Function Block To Receive A Measurand Value Goosemvrcv; Identification; Functionality; Function Block - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 13
Station communication
13.5
GOOSE function block to receive a measurand value
GOOSEMVRCV
13.5.1

Identification

Function description
GOOSE function block to receive a
measurand value
13.5.2

Functionality

GOOSEMVRCV is used to receive a measured (analog) value using IEC 61850 protocol via
GOOSE.
13.5.3

Function block

BLOCK
D0E13795T201305151403 V1 EN-US
Figure 156: GOOSEMVRCV function block
13.5.4

Signals

Table 318: GOOSEMVRCV Input signals
Name
BLOCK
Table 319: GOOSEMVRCV Output signals
Name
MVOUT
DATAVALID
COMMVALID
TEST
13.5.5

Settings

Table 320: GOOSEMVRCV Non group settings (basic)
Name
Operation
352
GOOSEMVRCV
^MVOUT
DATAVALID
COMMVALID
TEST
IEC10000251-1-en.vsd
Type
BOOLEAN
Type
REAL
BOOLEAN
BOOLEAN
BOOLEAN
Values (Range)
Unit
Off
-
On
© 2021 Hitachi Energy. All rights reserved.
IEC 61850
IEC 60617
identification
identification
GOOSEMVRCV
-
Default
Description
0
Block of function
Description
Measurand value output
Data valid for measurand value output
Communication valid for measurand value output
Test output
Step
Default
-
Off
1MRK 511 557-UEN Rev. A
D0E7445T201305151403 v1
ANSI/IEEE C37.2
device number
-
D0E7460T201305151403 v2
D0E7453T201305151403 v1
D0E7514T201305151403 v1
D0E7515T201305151403 v1
D0E7516T201305151403 v1
Description
Operation Off/On
Technical Manual