Section 12
Monitoring
12.22.4

Signals

Table 294: CBLEARN Input signals
Name
BLOCK
CMDOPEN
CMDCLOSE
CMDOPL1
CMDOPL2
CMDOPL3
CMDCLL1
CMDCLL2
CMDCLL3
INPNOL1
INPNOL2
INPNOL3
INPNCL1
INPNCL2
INPNCL3
INPPRIL1
INPPRIL2
INPPRIL3
CBTMD
ACPTLO
REJLO
FINISH
ABORT
Table 295: CBLEARN Output signals
Name
OPAVGNOL1
OPAVGNOL2
OPAVGNOL3
OPAVGNCL1
OPAVGNCL2
OPAVGNCL3
OPAVGPRIL1
Table continues on next page
332
Type
Default
Description
BOOLEAN
0
Block of the function
BOOLEAN
0
Open command issued by user
BOOLEAN
0
Close command issued by user
BOOLEAN
0
Open command input from SSCPOW for phaseL1
BOOLEAN
0
Open command input from SSCPOW for phaseL2
BOOLEAN
0
Open command input from SSCPOW for phaseL3
BOOLEAN
0
Close command input from SSCPOW for phaseL1
BOOLEAN
0
Close command input from SSCPOW for phaseL2
BOOLEAN
0
Close command input from SSCPOW for phaseL3
BOOLEAN
0
NO contact feedback from circuit breaker phaseL1
BOOLEAN
0
NO contact feedback from circuit breaker phaseL2
BOOLEAN
0
NO contact feedback from circuit breaker phaseL3
BOOLEAN
0
NC contact feedback from circuit breaker phaseL1
BOOLEAN
0
NC contact feedback from circuit breaker phaseL2
BOOLEAN
0
NC contact feedback from circuit breaker phaseL3
BOOLEAN
0
Primary contact feedback from circuit breaker phaseL1
BOOLEAN
0
Primary contact feedback from circuit breaker phaseL2
BOOLEAN
0
Primary contact feedback from circuit breaker phaseL3
BOOLEAN
0
Command input for activating CB test mode
BOOLEAN
0
Accept the last operation and corresponding calculations
BOOLEAN
0
Reject the last operation and corresponding calculations
BOOLEAN
0
Finish the CB test mode and accept learnt values as final values
BOOLEAN
0
Finish the CB test mode and reject learnt values
Type
Description
REAL
Average value of NO contact operating time till the last accepted
open operation for phaseL1
REAL
Average value of NO contact operating time till the last accepted
open operation for phaseL2
REAL
Average value of NO contact operating time till the last accepted
open operation for phaseL3
REAL
Average value of NC contact operating time till the last accepted
open operation for phaseL1
REAL
Average value of NC contact operating time till the last accepted
open operation for phaseL2
REAL
Average value of NC contact operating time till the last accepted
open operation for phaseL3
REAL
Average value of primary contact operating time till the last
accepted open operation for phaseL1
© 2021 Hitachi Energy. All rights reserved.
1MRK 511 557-UEN Rev. A
PID-6446-INPUTSIGNALS v1
PID-6446-OUTPUTSIGNALS v1