2.8
Connection Power Unit
2.8.1
Mains and motor connection
Absolutely pay attention to the supply voltage of the KEB COMBIVERT. A 230 V unit
at 400 V mains is destroyed immediately.
Exchanging mains and motor connection leads to immediate destruction of the unit.
Pay attention to the supply voltage and the correct polarity of the motor !
L1
L2
L3
PE
Legend
Legend
1
Mains supply
2
Mains fuse
3
Mains contactor
4
Mains choke
5
HF filter
6
KEB COMBIVERT
7
Motor (see also 2.8.3)
8
Motor protection temperature sensor (also see 2.8.4)
+U
-U
1
DC supply
2
DC fuses
3
Mains contactor
4
KEB COMBIVERT with DC input
5
Motor (see also 2.8.3)
6
Motor protection temperature sensor (also see 2.8.4)
Connection Power Unit
T1 T2
L1
L2
L3
PE
T1 T2
PE
++
U
V
--
W
PE
7
PE
PE
U
U
V
V
W
W
PE
U
V
W
8
GB - 25