Technical Specifications - Ablerex KRONOS Installation And Operation Manual

208v 10-40kv aups
Table of Contents

Advertisement

7. Technical Specifications

Capacity
Input
Voltage
Voltage Tolerance
Frequency
Power Factor
THDi
Output
Voltage
Voltage Tolerance
Frequency
Frequency
Tolerance
Power Factor
Crest Factor
Voltage Harmonic
Distortion
Overload
Bypass
Voltage
Voltage Tolerance
Frequency
Frequency
Tolerance
Battery
Number of batteries
100%
Max.
Load
Charging
<60%
Current(1)
Load
Common Battery for
Parallel
Configuration
Internal Battery
7/9Ah 20pcs x 2
Maximum Efficiency
VFI Mode
ECO Mode
Backup
Provides more charging current with less load condition.
(1)
10kVA
15kVA
±20% @100% load, -40% ~-20% @50% load
Output capacity decrease linearly according to the input voltage
110% for 60 minutes, 125% for 10 minutes, 150% for 1minutes
(<105% overload continuously without alarm, >= 105% <110% continuously with alarm)
Preventive range ±10% (Adjustable ±5% ~ ±15%)
Critical range ±25% (Adjustable ±16% ~ ±30%)
3.5A
5A
10A
15A
Available for
housing 12V
Available for housing 12V 7/9Ah
strings
93.5%
94%
92.5%
94%
20 kVA
208V
3 Phase + N
LL
40 ~ 70Hz
≧ 0.99
≦3% @ 100% load
200/208/220V 3 Phase + N
±1% (Static Load)
50/60Hz
±1% (free running)
1.0
3:1
≦1.5% with linear load
≦5% with distorting load
200/208/220V 3 Phase + N
50/60Hz
±1Hz / ±3Hz (Selectable)
12V,16/18/20pcs configurable
7A
21A
Yes
20pcs x 3 strings
94.5%
98%
94.5%
65
30kVA
40kVA
10A
13A
31A
42A
N.A
94.6%
94.6%
93.5%
94.3%