Ablerex KRONOS Installation And Operation Manual page 61

208v 10-40kv aups
Table of Contents

Advertisement

The UPS parameters that can be modified by the user using the control panel are listed in the
table below.
Parameters
Independent/Common
Total cell number
Capacity
Voltage Temperature compensation
Detect the Battery connecting
Battery
Charger current
CV Charger voltage [V/cell]
FV Charger voltage [V/cell]
Vbatt. Low [V/cell]
Vbatt. Min [V/cell]
Battery test 2 minutes
Output voltage
Output frequency
Output
Fine adjustment voltage
Input transformer
Input transformer ratio
Transformer
Output transformer
Output transformer ratio
Unit number
Number of units in parallel system
Other
Set EPO logic
(1) Transformer ratios can be calculated as following,
Input transformer ratio = Vp_in/Vs_in; Output transformer ratio = Vs_out/Vp_out
Content
(1)
(1)
Vp_in
Vs_in
UPS
Input
Transformer
Range
Ind. / Common
96 ~ 120
1~1000
Yes / No
Yes / No
0.0~1.0
2.000~2.550
2.000~2.550
1.850 ~ 1.883
1.600 ~ 1.900
Yes / No
115、120、127
50、60
-8 ~ 8
No / Mains & Bypass
0.00~10.00
No / Yes
0.00~10.00
1 ~ 6
1 ~ 6
NO/NC
Vp_out
Vs_out
Output
Transformer
59
Default
Common
120
88
No
Yes
0.1
2.300
2.250
1.850
1.670
Yes
120
50
0
No
0
No
0
1
1
NO