8.4 SNMP Cards

8.4.1 Megatec SNMP card
8.4.1.1 For installation please refer to the user's manual that came with the card.
8.4.1.2 Installation Position: Optional slot on rear panel
8.4.2 USB
The USB communication protocol definition is as below.
Complies with USB version 1.0, 1.5 Mbps.
1.
Complies with USB HID version 1.0.
2.
Pin Assignments:
3.
1 Æ VCC (+5V)
2 Æ D-
3 Æ D+
4 Æ Ground
38

9. Specifications Convertible Type (Rack / Tower)

MODEL
ITEM
VA
CAPACITY
W
Voltage Rating
Frequency Rating
Phase
INPUT
Power Factor
Generator Input
Input Connection
Voltage
Voltage Regulation
Frequency
(Synchronized Range)
Frequency
(Battery Mode)
Current Crest Ratio
Harmonic Distortion
Output Waveform
Outlets
Output
Overload Capacity
(tolerance
)
±
1 %
ARES RT-1K
ARES RT-2K
1000 VA
2000 VA
when input voltage is 180~300Vac PF=0.9 (900/ 1800/ 2700W)
110/150/180~300 VAC
(Based on load percentage0 ~ 60% / 0 ~ 75% / 0 ~ 100%)
45-65 Hz
Single phase with ground
0.99 (with full linear load)
Supported
10 A,
10 A,
IEC 320-C14
IEC 320-C14
230 V, adjustable to 200/208/220/230/240
within ±1% until low-battery warning
3 Hz or 1 Hz (selectable)
50/60 Hz ±0.2% unless synchronized to line
3:1
< 3% at full linear load
< 7% at full non-linear load
Pure sine wave
(3) 10 A,
(6) 10 A,
IEC 320-C13
IEC 320-C13
Line Mode:
1 05%continuous
106-120% for 30 seconds transfer to bypass.
121-150% for 10 seconds transfer to bypass.
1 50
Immediately transfer to bypass.
Buzzer continuously alarms.
Battery Mode :
1 05
continuous
106-120
for 30 seconds shuts down
121-150
for 10 seconds shuts down
1 50
Immediately shuts down.
Buzzer continuously alarms.
39
ARES RT-3K
3000 VA
16 A,
IEC 320-C20
(6) 10A, IEC
320-C13
+
(1) 16A IEC
320-C19