Ablerex MSRT-Pro 1KVA User Manual

Intelligent true on-line ups for corporate & it user
Hide thumbs Also See for MSRT-Pro 1KVA:

Advertisement

Intelligent True On-Line UPS
For Corporate & IT User
User manual
1K/1.5K/2K/3KVA

Table of Contents

1.
Important Safety Instruction....................................................................2
1.1. An Important Notice................................................................................2
1.2. Storage Instruction .................................................................................3
2.
Product Introduction ...............................................................................4
2.1. General Characteristics ..........................................................................4
2.2. Special Features.....................................................................................5
3.
UPS Functional Descriptions..................................................................6
3.1. UPS Front Panel Display Descriptions...................................................6
3.2. Real Panel Descriptions .........................................................................9
3.4. Communication Port Explanation .........................................................15
4.
Installation and Operation.....................................................................17
4.1. Unpacking.............................................................................................17
4.2. Selecting Installation Position...............................................................18
4.3. Set up ...................................................................................................19
4.4. Operation ..............................................................................................23
5.
UPS Working Principle .........................................................................36
5.1. UPS System Block Diagram.................................................................36
5.2. When Utility is Normal ..........................................................................37
5.3. When Utility is Abnormal/Absent ..........................................................38
5.4. Overload Condition...............................................................................39
5.5. Inverter Failure .....................................................................................40
5.6. Inverter/Internal Over temperature .......................................................41
5.7. Inverter Over.........................................................................................41
6.
Maintenance Guide ..............................................................................42
6.1. Trouble Shooting ..................................................................................42
6.2. Error Codes and Their Descriptions .....................................................44
6.3. Maintenance .........................................................................................45
7.
Bundle Software Installation Guide ......................................................46
7.1. Hardware Installation............................................................................46
7.2. Software Installation .............................................................................46
8.
Optional Communication Cards ...........................................................47
8.1. R2E (2nd RS-232 ) card .......................................................................47
8.2. USE (USB) card ...................................................................................47
8.3. DCE (Dry Contact) card........................................................................48
8.4. SNMP Cards.........................................................................................49
9.
Specifications .......................................................................................50
1

Advertisement

Table of Contents
loading

Summary of Contents for Ablerex MSRT-Pro 1KVA

  • Page 1: Table Of Contents

    Table of Contents Important Safety Instruction..............2 1.1. An Important Notice................2 1.2. Storage Instruction .................3 Product Introduction ................4 2.1. General Characteristics ................4 2.2. Special Features..................5 UPS Functional Descriptions..............6 3.1. UPS Front Panel Display Descriptions...........6 3.2. Real Panel Descriptions .................9 3.3. Operating Modes & Voltage System Configurations......11 3.4.
  • Page 2: Important Safety Instruction

    Important Safety Instruction 1.2. Storage Instruction For extended storage in moderate climate, the batteries should be charged 1.1. An Important Notice for 12 hours every 3 months interval by connecting the UPS to the utility supply SAVE THESE INSTRUCTIONS - This Manual Contains Important and switch on input breaker located at UPS rear panel.
  • Page 3: Product Introduction

    Product Introduction 2.2. Special Features 1. High Frequency Transformer-less technology with rack/tower convertible 2.1. General Characteristics enclosure enables the UPS for integration even in the most difficult of environment with space constraints. True online technology continuously supplies your critical device with a stable, regulated, transient-free pure sine wave AC Power.
  • Page 4: Ups Functional Descriptions

    UPS Functional Descriptions 3.1. UPS Front Panel Display Descriptions LCD Display Green LED steadily lights up to indicate that the Utility input voltage is within 3.1.1. LCD panel (Optional) the window (80Vac~144Vac, or 160Vac~288Vac); the LED flashes flickeringly to indicate that the Utility input voltage is within the acceptable window (60Vac~79Vac, or 120Vac~159Vac).
  • Page 5: Real Panel Descriptions

    3.1.2.1 Symbols on the LCD Display Panel 3.2. Real Panel Descriptions 120V Item Symbol Description 1/1.5KVA LINE Utility or Bypass Source Battery Low Battery Abnormal UPS Overloading 2KVA Site Wiring Fault UPS Working in Service Mode UPS Shutoff 3KVA FAIL UPS Abnormal Lock UPS Flow Chart 4 Digits Measurement Display...
  • Page 6: Operating Modes & Voltage System Configurations

    3.3. Operating Modes & Voltage System Configurations 230V Download and open the “UPS Setting Tool” Software to see the screen as below 1/1.5KVA 2KVA 3KVA 1. USB Port 2. RS232 Port 3. Emergency Power Off (EPO) Dry Contact Signal inputs 3.3.1.
  • Page 7 5. Bypass Voltage Windows:Sensitivity: Select Sensitivity Low/Sensitivity 3.3.2. Programmable outlet setting High** The UPS is equipped with 2 programmable outlets for use to supply to less Sensitivity Low Sensitivity High critical loads. These outlets can be disabled to shed the less critical loads during 110V System 90V~130V 97V~130V...
  • Page 8: Communication Port Explanation

    1. Outlet Turn On After Turn on UPS – select the time to automatically 3.4. Communication Port Explanation enable this outlet within the specified time when the UPS is powered on. If “0” sec is selected, the outlet will be enabled once the UPS is powered on. The UPS is equip with EPO dry contacts input, true RS232 &...
  • Page 9: Installation And Operation

    Installation and Operation The Pin Assignments of the true RS232 port are illustrated as follows: Read the Safety Instruction guide (page 2 to 3) before installing the UPS 4.1. Unpacking Inspect the UPS upon receipt. The manufacturer designed robust packaging for your product.
  • Page 10: Selecting Installation Position

    4.3. Set up 4.2. Selecting Installation Position Tower Configuration Setup The UPS is heavy. Select a location sturdy enough to handle the UPS weight. Step 1 To ensure proper operation and long operating life, always position the UPS according to the following requirement: 1.
  • Page 11 Rack-Mount Configuration Setup Power Module + Battery Module Step 1 Step 1 Step 2 Step 2 Step 3...
  • Page 12: Operation

    Step 4 4.4. Operation 4.4.1. LED panel (Standard) 4.4.1.1 Start Up in Normal AC Mode 1. Before commencing the installation, please ensure the grounding is connected properly. 2. Ensure the voltage of Utility matches with the input voltage window of the UPS.
  • Page 13 4.4.1.3 Shutdown 1. Shutdown in AC Mode: Press the ‘ ’ Switch for approximate 5 seconds until the buzzer beeps, the UPS will stop power supply to the outlets. The all LEDs light off and the ventilating fans shall continue to operate. Switch Off the AC power source, the ventilating fans shall stop to operate after 10 sec.
  • Page 14 (6) Your start-up operation of the UPS is completely now as illustrated as 4.4.2.3 Check Measured Values & Figures detected by UPS drawing E. Make sure the UPS is plugged onto the wall receptacle for (1) If you would like to check the measured values & messages, please use charging at least 4 hours and the batteries of the UPS are fully charged scroll up and scroll down...
  • Page 15 4.4.2.4 UPS Default Data and Special Function Execution (1) After UPS is turned on successfully, use key pad to change the LCD Display screen to drawing P1. (2) Press key pad to scroll down the LCD screen, then check the UPS settings.
  • Page 16 (3) Press scroll up key pad, you may execute special functions. The functions include Buzzer ON (as drawing P1) or buzzer OFF (as drawing P2, Alarm silence for UPS warning) and self-test ON (as Drawing Q1) or OFF (as Drawing Q2. UPS will execute battery test for 10 seconds), if the self-test is successful, it show as Drawing W;...
  • Page 17 4.4.2.7 Shut Off (1) Press key pad for about 5 seconds, the Inverter output will be turned off, the UPS will stop power supply to the outlets and the LCD screen shows as drawing B. (2) Turn off the input of the UPS. (3) The UPS is turned off completely.
  • Page 18 Step 3 4.4.4. Battery Replacement Step 1 Step 4 1/1.5KVA 2K/3KVA Step 2...
  • Page 19: Ups Working Principle

    UPS Working Principle Utility LEDs Display UPS Operating Modes Conditions indications Rectifier convert AC to DC, battery 5.1. UPS System Block Diagram charging, Inverter convert DC to AC LEDs Utility Normal and supply to loads with clean & stable remain illuminated power.
  • Page 20: When Utility Is Abnormal/Absent

    5.3. When Utility is Abnormal/Absent 5.4. Overload Condition The working principle of the UPS under Utility abnormal condition is illustrated The working principle of the UPS when overloading is illustrated as follows: as follows: Fig 5.4 Fig 5.3 1. Generally modern day electronics & IT equipment generate an inrush current when switching on.
  • Page 21: Inverter Failure

    2. The UPS Bypass loop is also equipped with overload protection. Its overload 5.6. Inverter/Internal Over temperature capacity is illustrated by the graph & table below. If the UPS experiences internal over-temperature when Utility is normal, it will switch to bypass loop. The UPS will switch back to inverter mode when the over-temperature situation is eliminated.
  • Page 22: Maintenance Guide

    UPS fails to provide If the backup time remains non- battery backup or its satisfactory after 4 hours of Maintenance Guide back up time is shorter charging, please contact your than its intended local dealer for battery 6.1. Trouble Shooting performance.
  • Page 23: Error Codes And Their Descriptions

    6.2. Error Codes and Their Descriptions 6.3. Maintenance Clean the dust from the ventilation openings and intakes on the rear panel. Code Descriptions 1. Turn off the UPS and wipe the casing with a damp cloth. Er05 Battery weak or faulty 2.
  • Page 24: Bundle Software Installation Guide

    Bundle Software Installation Guide Optional Communication Cards 7.1. Hardware Installation 8.1. R2E (2nd RS-232 ) card 1. Connect the male connector of RS232/USB* cable to the UPS communication port. 2. Connect the female connector of the RS232/USB* cable to a dedicated RS232 port of the Computer.
  • Page 25: Dce (Dry Contact) Card

    8.3. DCE (Dry Contact) card 8.4. SNMP Cards 8.4.1. SNMP/WEB card 8.3.1. The pin assignments of 10-Pin Terminal: 8.4.1.1 For installation, please refer to the user’s manual attached with the UPS on Bypass mode (Bypass) card. Utility Normal (Normal close contact) 8.4.1.2 Installation Position:Optional Slot Utility Normal (Normal open contact) Inverter On...
  • Page 26: Specifications

    Frequency(Battery ±0.1% (0.05~0.06Hz) unless synchronized to line Specifications Mode) PF=0.7 Current Crest Factor Model 1KVA 1.5KVA 2KVA 3KVA PF=0.8 2.7:1 1KVA,2KVA, 3KVA≦3% THD(Linear Load) VA Rating Harmonic Distortion 1.5KVA≦4% THD(Linear Load) Apparent Output Power 1000VA 1500VA 2000VA 3000VA ≦7% THD(Non-Linear Load) PF=0.7 700Watts 1050Watts...
  • Page 27 (AC Mode ) <105% continuous Physical >106%~120% for 30 seconds transfer to bypass 88(2U)x440x 88(2U)x440x 88(2U)x440x Dimensions(HxWxD in mm) 88(2U)x440x 650 >121%~150% for 10 seconds transfer to bypass >150% for immediately transfer to bypass 115V 34.5Ib(15.7kg) 34.5Ib(15.7kg) 61.3lb(27.9kg) 68.6Ib(31.2kg) Weights Buzzer continuously alarms.
  • Page 28 192321132048001...