Specifications - Ablerex Mars II User Manual

Table of Contents

Advertisement

7. Specifications

UPS Model
Voltage Window
Frequency
Phase/Wire
Power Factor
Current THD (100% linear load)
Voltage Window
Voltage Adjustment
Voltage Regulation
Capacity
Rated Power Factor
Wave Form
Frequency Stability
Frequency Regulation
Transfer Time
Crest Factor
Efficiency (AC to AC, Normal)
Efficiency (AC to AC, ECO)
Autonomy
DC Start
Type
Quantity
Voltage
Recharge Time
Status On LED + LCD
Readings on LCD
Self-Diagnostics
Audible and Visual
Dimensions
WxDxH (mm)
Input/Output Connection
External Battery Connection
Net Weight (kg)
Operating Temperature
Temperature Warning
Altitude
Humidity
Noise
Interface Type
Communication Slots
Quality Assurance
Safety Standard
EMC Standard
Marks
Specifications are subject to change without prior notice.
INPUT
OUTPUT
60 pcs
80 pcs
BATTERY (External Battery Bank)
Without TX
With TX
DISPLAY
Line Mode, Backup Mode, ECO Mode, Bypass Supply, Battery Low, Battery
Bad/Disconnect, Overload, Transferring with interruption, UPS Fault
Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load
Upon Power-on, Front Panel Setting & Software Control, 24-hour routine checking
ALARMS
Line Failure, Battery Low, Transfer to Bypass, System Fault Conditions
PHYSICAL
Without TX
With TX
Without TX
With TX
ENVIRONMENT
The battery design life is based on a temperature of 25 C. Ambient temperature
COMPUTER INTERFACE
2
RS232, USB, RS485, Relay Contact (DCE), SNMP/WEB Card, etc.
nd
SAFETY CONFORMANCE
13
AB-MSII20000
160-280 VAC (1Φ)
45-65 Hz
Single-Phase, Line1 + Line2 + PE
>0.9 (0.95)
<30%
220/230/240 VAC Selectable (208/120 VAC optional)
±0%, ±1%, ±2%, ±3%
±2%
20000 VA/18000 W
0.9 Lagging
Sine Wave, THD<3% (no load to full load)
±0.2% (Free Running)
±1Hz, ±3Hz
0 ms
3:1 acceptable
Up to 91%
Up to 96%
≥ 7 min.
≥ 11 min.
Yes
Sealed Lead Acid Maintenance Free
12V/9Ah x 60pcs
12V/9Ah x 80pcs
240 VDC
6 Hours to 90%
Percentage, Battery Voltage, Inner Temperature.
290 x 645 x 748 mm
320 x 670 x 1018 mm
Hard-wired
Plug-in & Play
60
151
0 C to 40 C
above this range will reduce battery life.
0~2000m up to 40 C, 3000m up to 35 C
90% RH Maximum, Non-Condensing
<60dB (at 1 meter)
Standard RS232 Interface
ISO9001 Certified Company
EN62040-1-1,
EN62040-2, EN61000-3-4, EN61000-3-5,
CE