Installation And Wiring; Storage And Installation Environment - Ablerex KRONOS Installation And Operation Manual

208v 10-40kv aups
Table of Contents

Advertisement

2.

Installation and Wiring

2.1 Storage and Installation Environment

 Storage Environment
 Temperature-20℃~70℃
 Relative Humidity≦95%
 Installation Environment
A proper installation environment not only ensures the effective operation of the UPS but it
also reduces the chance of failure and extends service life. Take the following
recommendations into account when selecting a suitable environment. This will also
minimize any potential accidents.
 This product must be use in a CONTROLLED ENVIRONMENT.
 Temperature0℃~40℃ (20℃~25℃is recommended for extend batteries life time).
 Relative Humidity ≦95% (without condensation)
 Altitude1000m at normal power. Over 1000m above sea level, the maximum output
current must be derated by 1% every additional 100m.
 This product must not be used in an environment with sparks, smoke or gas to prevent
arcing, injury and fire hazards.
 Avoid using dusty materials, volatile gases, or corrosive substances with a high salt-
content in the environment where the UPS is installed.
 The installation location of the UPS must be well-ventilated. During charging, the
chemical reaction of the battery generates small amounts of gases. A crack in the any of
the batteries may pose an environmental hazard.
 Do not place in a location near a heat source as this will shorten the battery life.
 Do not place outdoors and avoid direct exposure to sunlight.
 Always ensure that the environment where the UPS is located is free from animals that
may damage the wiring, such as rats and domestic pets.
 Always ensure that the floor is designed enough to support the UPS and battery. The must
meet the minimum requirements for floor weighting to prevent failure and injury.
 We recommend placing a fire extinguisher near the UPS in case of an emergency.
20