3.4.1 Normal Mode Start-up
(1) On the rear of UPS, switch ON the AC Power switch.
(2) Close UPS Mains Input Breaker/Switch and Bypass Input Breaker if equipped.
(3) Select
→Command→Operation→Normal Mode on LCD display.
(4) Return to the Mimic Display. Wait for few minutes, the rectifier will have started.
(5) Close the battery switch/fuses to connect the batteries after rectifier has been turned on.