Ablerex MSII-RT User Manual

Parallel redundancy on-line ups 6kva

Advertisement

ablerex MSII-RT
Parallel Redundancy On-Line UPS
User's Manual
1.
Important Safety Instruction....................................................................2
1.1. An Important Notice................................................................................2
1.2. Storage Instruction .................................................................................4
2.
Product Introduction ...............................................................................5
2.1. General Characteristics ..........................................................................5
2.2. Symbols on the LCD Display Panel .......................................................7
2.3. Panel explanation ...................................................................................9
2.4. Communication Port Explanation .........................................................11
3.
Installation and Operation.....................................................................12
3.1. Unpacking.............................................................................................12
3.2. Selecting Installation Position...............................................................13
3.3. Installation of Casters Cover ................................................................14
3.4. Terminal Block Explanation ..................................................................20
3.5. Operation Test and Installation Instruction...........................................27
4.
Troubleshooting Guide .........................................................................38
4.1. Trouble Shooting ..................................................................................38
5.
Bundled Software Installation Guide ....................................................40
5.1. Hardware Installation............................................................................40
5.2. Software Installation .............................................................................40
6.
Customer Options Slots........................................................................41
6.2. R2E(2nd RS-232 ) card ........................................................................41
6.3. RSE(RS-485) card................................................................................41
6.4. USE(USB) card ....................................................................................41
6.5. DCE(Dry Contact) card.........................................................................42
6.6. SNMP Cards.........................................................................................43
6.7. The Installation of those Interface Cards..............................................43
7.
Hot Swappable Battery Replacement ..................................................45
8.
Specifications .......................................................................................47
6Kva

Table of Contents

1

Advertisement

Table of Contents
loading

Summary of Contents for Ablerex MSII-RT

  • Page 1: Table Of Contents

    5.1. Hardware Installation................40 5.2. Software Installation ................40 Customer Options Slots................41 6.1. All the below interface cards are with built-in EPO function....41 ablerex MSII-RT 6.2. R2E(2nd RS-232 ) card ................41 6.3. RSE(RS-485) card................41 6.4. USE(USB) card ..................41 6.5. DCE(Dry Contact) card.................42 6.6.
  • Page 2: Important Safety Instruction

    1.1.14. If liquids are split onto the UPS or foreign objects dropped into the unit, 1. Important Safety Instruction the warranty will be null and void. 1.1. An Important Notice 1.1.15. The battery will discharge naturally if the system is unused for any length of time.
  • Page 3: Storage Instruction

    branch circuit over-current protection for 30 amperes rating in accordance 2. Product Introduction with the National Electric Code, ANSI/NFPA 70. 1.1.26. CAUTION - To reduce the risk of fire, unit input connect only to a circuit 2.1. General Characteristics provided with branch circuit over-current protection for 40 amperes rating in accordance with the National Electric Code, ANSI/NFPA 70.
  • Page 4: Symbols On The Lcd Display Panel

    2.2. Symbols on the LCD Display Panel 2.1.12. Revolutionary battery management circuit analyzes battery discharging status to adjust battery cut-off point and extend the life of batteries. Item Symbol Description 2.1.13. Intelligent temperature-controlled fan may not only extend the life of the LINE Utility or Bypass Source fan, but also reduce annoying noise because of sudden fan spin.
  • Page 5: Panel Explanation

    2.3. Panel explanation Next Page 2.3.1. Front Panel Function Explanations Special Function Log in /out Enter or Reconfirmed Utility Input Normal LED Bypass Input Normal LED UPS under Redundancy Mode UPS under ECO Mode UPS Fault or Abnormal Warning LED Emergency Power Off Er05 Battery Weak or Dead...
  • Page 6: Communication Port Explanation

    2.4. Communication Port Explanation Go to next page Go to previous page or change the setting of the UPS. The Communication port on the UPS provides true RS232 type to communicate with UPS software to remote monitoring the power and UPS status. To re-confirm the change of UPS Setting With optional interfaces cards, which contains R2E(2 RS232 plus EPO),...
  • Page 7: Installation And Operation

    3. Installation and Operation 3.2. Selecting Installation Position It is necessary to select a proper environment to install the unit, in order to The packing condition and the external outlook of the unit should be minimize the possibility of damage to the UPS and extend the life of the UPS. inspected carefully before installation.
  • Page 8 3.3. Installation 3.3.1 Tower installation 3.3.1.2 Power Module+ Isolation Transformer Module+ Battery Module 3.3.1.1 Power Module + Battery Module Step1: Installation of the Power Module, Isolation Transformer Module and Battery Step1: Installation of the Foot Covers of the Power Module Module Step2: Installation of the Power Module and the Battery Module...
  • Page 9 Step2: Installation of the Ear Covers to Power Module, Isolation Transformer Module 3.3.2 Rack installation and Battery Module 3.3.2.1 Power Module+ Battery Module Step1: Installation of the Ear Covers Step3: Installation of the Rail kit to Rack Cabinet...
  • Page 10 3.3.2.2 Power Module+ Isolation Transformer Module+ Battery Module Step1: Installation of the Isolation Transformer Module to the Rail Step5: Installation of the Power Module to the Rack Cabinet Step2 : Installation of the Power Module to the Rack Cabinet...
  • Page 11: Terminal Block Explanation

    3.4 Terminal Block Explanation 2. When the Maintenance Bypass Switch is installed: L12-N1: the terminal for Utility Input to provide the power source when the ● UPS is working under Utility mode. G1: the terminal for UPS Input Ground. ● L21、N22: the terminals for UPS Output.
  • Page 12 (3a1) c. For 200/100Vac, 220/110Vac, 230V/115Vac, or 240/120Vac system, You may connect as shown in below. (3a2) d. For 240/208/120Vac system, you may connect as shown in below. b. For 100/110/115/120Vac system, you may connect as shown in below.
  • Page 13 (4a2) 4. When the Isolation transformer is installed but Maintenance Bypass Switch isn’t installed: b. For 100/110/115/120Vac system, you may connect as shown in below. a. For 200/220/230/240Vac system, you may connect as shown in below. c. For 200/100Vac, 220/110Vac, 230V/115Vac, or 240/120Vac system, You may connect as shown in below.
  • Page 14: Operation Test And Installation Instruction

    3.5. Operation Test and Installation Instruction 3.5.1. Start Up in Normal Mode 3.5.1.1 Open the terminal block cover on the rear panel (refer to 2.3.2) Before start the installation, please make sure the grounding is connected properly. 3.5.1.2 Make sure Utility breaker, UPS’ Utility breaker is On “Off” position. 3.5.1.3 Make sure the voltage of Utility matches with the input voltage window of the UPS.
  • Page 15 3.5.1.9 Your start-up operation of the UPS is completely now. Make sure the UPS is plugged onto the wall receptacle for charging at least 8 hours and the batteries of the UPS are fully charged. 3.5.2 Start-up in Battery Mode (Cold Start) 3.5.2.1 Make sure the UPS you have has already been installed at least 1 set(20pcs) of 12V/7AH or 12V/5AH batteries.
  • Page 16 3.5.3 Check Measured Values & Figures detected by UPS 3.5.3.1 If you would like to check the measured values & figures detected by the UPS, please use scroll up and scroll down key pads. When you use scroll down key pad, the LCD display will illustrate as Drawing C(Voltage from Utility Input) Drawing I1(Voltage from Bypass Input) Drawing J(Frequency...
  • Page 17: Ups Default Data/Special Function Execution

    3.5.4 UPS Default Data and Special Function Execution 3.5.4.1 After UPS completely starts up, press key pad to change the LCD display screen to drawing Q1. * It shows self-test is “On”. * It shows buzzer “On”. * It shows Bypass Voltage is adjusted to narrow one. * It shows buzzer “Off”...
  • Page 18: Ups Default Settings

    * It shows Output Voltage Adjustment % from 0% to 3% or -0% to -3%. * It shows the UPS is operated in “normal mode”. * It shows UPS Identification Number. * It shows the UPS is operated in “Eco mode”. * It shows the UPS is in the No.
  • Page 19: Ups Is Off

    3.5.5.3 Except Buzzer(as drawing Q1 & Q2) and Self-test(as drawings R1 & R2), 3.5.5.13 Your Setting changes are complete. all the rest default settings may be changed by pressing scroll up key pad. 3.5.6 UPS Is Off Due to Unknown Reason and Its Trouble Shooting 3.5.5.4 Drawings S1 and S2 mean the bypass input acceptable window, it can be 3.5.6.1 If there is a serious abnormal condition occurred, the UPS will lock it itself 184Vac~260Vac or 195Vac~260Vac.
  • Page 20: Troubleshooting Guide

    4. Troubleshooting Guide Situation Check Items Solution UPS Red Fault LED Check the error code 1. Check to see if the battery 4.1. Trouble Shooting lights up shown on the LCD connection is properly done, screen then re-charge the batteries for When the UPS malfunctions during operation, you may check the followings: 8 hours to see whether the 1.Er05,...
  • Page 21: Bundled Software Installation Guide

    5. Bundled Software Installation Guide 6. Customer Options Slots 5.1. Hardware Installation 6.1. All the below interface cards are with built-in EPO function. 1. Connect the male connector of RS232 cable to the UPS communication port. The pin assignments of the EPO are: 2.
  • Page 22: Use(Usb) Card

    6.6. SNMP Cards 6.4. USE(USB) card 6.6.1. SNMP/WEB card For installation, please refer to the user’s 6.4.1. CN1 for USB and CN3 for EPO. manual attached with the card. . 6.4.2. For communication protocol, please Installation see the definition below: Position: slot1 or slot 2.
  • Page 23: Hot Swappable Battery Replacement

    Hot Swappable Battery Replacement 1. Remove the screw covers as well as screws as shown in Step 1. 2. Remove the front panel as indicated in Step 2. 3. Remove the screws of the battery module as shown in Step 3.
  • Page 24: Specifications

    8. Specifications 4. Unplug the hot swappable battery connectors as shown in Step 4. Model 4500VA 6000VA INPUT Voltage Window 160~280Vac* Frequency 45 ~ 65 Hz Phase/Wire Single, Line + Neutral + Ground Power Factor Up to 0.99 at 100% Linear Load Current THD <6% at 100% Linear Load OUTPUT...
  • Page 25 PHYSICAL Dimensions(WxDxH)mm 440x88x660(UPS Module) Input/Output Connection Hardwire External Battery Connection Plug-in & Play Net Weight(Kgs) 24(UPS Module) Battery Bank Dimensions Convertible(Rack/Tower) BBC20J0007(20pcs 12V/7AH) 440x133x660(3U) Battery Bank Net Weight Convertible(Rack/Tower) BBC20J0007 w/o bat./with bat. 18Kgs/68kgs Isolation Transformer 440x88x660(2U) Dimensions Isolation Transformer Net Convertible(Rack/Tower) Weight with Maintenance Bypass Switch.
  • Page 26 192321142000000...