Specifications

MODEL
ITEM
CAPACITY
VA / W
1000 VA/700 W
Voltage Rating
Frequency Rating
INPUT
Phase
Power Factor
Generator Input
Input Connection
10 A, IEC 320-C14
Voltage
Voltage
Regulation
Frequency
(Synchronized
Range)
Frequency
(Battery Mode)
Current Crest
Ratio
Harmonic
Distortion
Output Waveform
Outlets
10 A, IEC 320-C13
Line
mode
Output
Battery
mode
Overload
capacity
Bypass
mode
1K
2K
2000 VA/1400 W
3000 VA/2100 W
110/140/160-300 VAC (Based on load percentage
0-25% / 25-50% / 50-100%)
45-65 Hz
Single phase with ground
0.
98 (with full linear load)
Supported
10 A, IEC 320-C14
16 A, IEC 320-C20
230 V, adjustable to 200/208/220/230/240
within ±1% until low-battery warning
3 Hz or 1 Hz (selectable)
50/60 Hz ±0.1% unless synchronized to line
3:1
< 3% at full linear load
< 7% at full non-linear load
Pure sine wave
(3)
(6)
10 A, IEC 320-C13
10A, IEC 320-C13
<105% continuous
106-120% for 30 seconds transfer to bypass
121-150% for 10 seconds transfer to bypass
>150% Immediately transfer to bypass.
Buzzer continuously alarms.
<105% continuous
106-120% for 30 seconds shuts down
121-150% for 10 seconds shuts down
>150% Immediately shuts down.
Buzzer continuously alarms.
<105% continuous
106-120% for 250 seconds shuts down
121-130% for 125 seconds shuts down
131-135% for 50 seconds shuts down
136-145% for 20 seconds shuts down
146-148% for 5 seconds shuts down
149-157% for 2 seconds shuts down
158-176% for 1 seconds shuts down
177-187% for 0.32 seconds shuts down
for 0.16 seconds shuts down.
>188%
Buzzer continuously alarms.
30
Efficiency
3K
Battery
Transfer time
(6)
DC start
Self
Diagnostics
Front Panel
Audible Alarm
Protection
Line mode
90%
Battery mode
85%
ECO mode
96%
Number of
2
batteries
Battery type
12 V/7.2 Ah Sealed, non-spillage, maintenance-free, lead acid
Rated Battery
24 VDC
Voltage
Backup time (half
> 10 min.
load)
Backup time (full
> 3 min.
load)
Charge
Standard
2.2 A
Current
(Max.)
External
8.8 A
Recharge time (to
3hr
90%)
Floating Mode
27.4Vdc±1%
Charging Voltage
Bluk Mode
30.0Vdc±1%
Charging Voltage
DC leakage
≤ 30 µA with no AC applied and the unit in the off position
current
AC to DC
Inverter to Bypass
4 ms (Typical)
By panel button or software control
Load Level/Battery Level/ Battery Mode/ Normal Mode/Bypass
Standard
Mode/ Self-Test/ Weak/Bad Battery/Site Wiring Fault/ Fault/
LED
Optional
Programmable Outlet1/ Programmable Outlet2
Button
ON (Alarm Silence)/ OFF (Test/Level Button)
Battery Mode
Sounds once every 1.5 seconds
Low Battery
Sounds once every 0.2 seconds
Overload
Sounds once every 3 seconds
Normal alarm
Sounds once every 3 seconds
Fault
Continuous tone
Bypass mode : Fuse
Short Circuit
Normal Mode : Output Breaker/Electronic Circuit
Battery Mode : Output Breaker/Electronic Circuit
Battery
ABDM
EPO(Optional)
UPS shuts down immediately.
31
90%
90%
85%
85%
96%
96%
4
6
48 VDC
72 VDC
> 10 min.
> 10 min.
> 3 min.
> 3 min.
1.4 A
1 A
11.2 A
8 A
3hr
3hr
54.8Vdc±1%
82.2Vdc±1%
60.0Vdc±1%
90.0Vdc±1%
0 ms
4 ms (Typical) / 0 ms (Optional)
Yes
Overload