Timed; Run Time Control - Johnson Controls FRICK QUANTUM HD Operation

Control panel
Hide thumbs Also See for FRICK QUANTUM HD:
Table of Contents

Advertisement

ACCESSING:
DESCRIPTION: This screen may be used to assign a digital
output to run based on the Compressor Run time.
RUN TIME DIGITAL OUTPUT CONTROL
Timed Output C - (Off or On status shown)
Enable
Disable - Output C will not be
enabled.
Enable - Output C will turn on after
the Output On times have been
met.
I/O Board - Three selections are provided:
None - No board selected.
QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
CONFIGURATION
Digital Auxiliaries - Timed - Run Time Control
Digital Auxiliaries
090.040-O (MAR 12)

Timed

Run Time Control

Digital Board 1 - The Output to
be controlled is located on Digital
Board 1.
Digital Board 2 - The Output to
be controlled is located on Digital
Board 2.
Output On Every - The number of hours
after the Compressor has been running,
before the Output will energize.
Output On Time - The length of time that
the Output will be energized once the Run
Hour Interval has been satisfi ed.
I/O Channel - Enter the channel of the
selected Digital Board to control (1 - 24).
Page 97