ACCESSING:
DESCRIPTION: Use this screen to confi gure the PI Control
channels. There are eight total screens associated with PI
Confi guration (PI A - H), and all screens consists of the
same layout:
CHANNEL CONFIGURATION
[Name] - A user defi ned name can be entered
here.
[Control Input] - A pop-up box is provided to
select from the following:
•
Capacity Slide Position
•
Volume Slide Position
•
Suction Pressure
•
Discharge Pressure
•
Compressor Oil Pressure
•
Main Oil Injection Pressure
•
Economizer Pressure
•
Filter Pressure
•
Intermediate Pressure
•
Balance Piston Pressure
•
System Discharge Pressure
•
Suction Temperature
•
Discharge Temperature
•
Compressor Oil Temperature
•
Oil Separator Temperature
•
Process/Brine Temperature Leaving
•
Process/Brine Temperature Entering
•
Remote Control Setpoint
•
Motor Current
•
RPM
QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
CONFIGURATION
Proportional / Integral Control
Proportional/Integral Control
Setup
PI Control 1
•
Auxiliary Analog #1 - #20
•
Manifold Pressure
•
Remote Capacity Position
•
Compressor Vibration – Suction
•
Compressor Vibration – Discharge
•
Motor Vibration – Shaft Side
•
Motor Vibration – Opposite Shaft Side
•
Motor Temperature – Shaft Side
•
Motor Temperature – Opposite Shaft
Side
•
Motor Stator #1 - #3
•
Vyper Coolant Temperature
[Control] - A pull down menu is provided to
select from the following:
•
Disabled - No PID control.
•
Running - PID Control only controls
when the compressor is running.
•
Active - PID control always active.
PI CONFIGURATION
[Action] - A pop-up box is provided to select
from the following:
•
Forward - Will increase the output at
values greater than the Control Set-
point.
•
Reverse - Will increase the output at
values less than the Control Setpoint.