Proportional / Integral Setup - Johnson Controls FRICK QUANTUM HD Operation

Control panel
Hide thumbs Also See for FRICK QUANTUM HD:
Table of Contents

Advertisement

ACCESSING:
DESCRIPTION: Use this screen to confi gure the PI Control
channels. There are eight total screens associated with PI
Confi guration (PI A - H), and all screens consists of the
same layout:
CHANNEL CONFIGURATION
[Name] - A user defi ned name can be entered
here.
[Control Input] - A pop-up box is provided to
select from the following:
Capacity Slide Position
Volume Slide Position
Suction Pressure
Discharge Pressure
Compressor Oil Pressure
Main Oil Injection Pressure
Economizer Pressure
Filter Pressure
Intermediate Pressure
Balance Piston Pressure
System Discharge Pressure
Suction Temperature
Discharge Temperature
Compressor Oil Temperature
Oil Separator Temperature
Process/Brine Temperature Leaving
Process/Brine Temperature Entering
Remote Control Setpoint
Motor Current
RPM
QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
CONFIGURATION
Proportional / Integral Control
Proportional/Integral Control
Setup
PI Control 1
Auxiliary Analog #1 - #20
Manifold Pressure
Remote Capacity Position
Compressor Vibration – Suction
Compressor Vibration – Discharge
Motor Vibration – Shaft Side
Motor Vibration – Opposite Shaft Side
Motor Temperature – Shaft Side
Motor Temperature – Opposite Shaft
Side
Motor Stator #1 - #3
Vyper Coolant Temperature
[Control] - A pull down menu is provided to
select from the following:
Disabled - No PID control.
Running - PID Control only controls
when the compressor is running.
Active - PID control always active.
PI CONFIGURATION
[Action] - A pop-up box is provided to select
from the following:
Forward - Will increase the output at
values greater than the Control Set-
point.
Reverse - Will increase the output at
values less than the Control Setpoint.