090.040-O (MAR 12)
Page 88
ACCESSING:
DESCRIPTION: Use this screen to set the Leaving Process
Safeties.
LEAVING PROCESS SAFETIES
•
Disabled
•
Enabled
The following setpoint boxes are provided:
Load Inhibit
•
Warning - If the Leaving Process
Temperature greater than or equal
to this setpoint, for the warning
QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
CONFIGURATION
Capacity Control - Leaving Process Safeties
Capacity Control
time delay, a warning occurs.
•
Delay - This is the delay period for
the Load Inhibit Warning.
Force Unload
•
Warning - If the Leaving Process
Temperature is greater than or
equal to this setpoint, for the alarm
time delay, a warning occurs.
•
Delay - This is the delay period for
the Force Unload Warning.
Leaving Process Safeties