ACCESSING:
DESCRIPTION: Use this screen to set the specifi c Drive
safeties information for a Vyper motor starter. These
safeties are important for the safe operation of the com-
pressor and motor.

VYPER CONTROL

Standby Time - The amount of time after the
compressor is stopped that the Vyper will keep
the DC Bus charged to quickly react to Start
commands.
Time Remaining - The time remaining for stand-
by time once the standby time expires, allowing
the DC Bus to discharge.
Command Rate - The frequency of communica-
tions per second.
QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
CONFIGURATION
Drive - Vyper Control
Drive
Vyper
Self Clearing Vyper Faults - Many Vyper faults
are self-clearing. If the Self-Clearing Faults has
been enabled, the Vyper can clear faults and be
re-started if needed.
Disabled
Enabled
Clear Total kWh - Clears the total KiloWatt
hours accurued by the Vyper.
Clear VSD Fault Memory - Clears the VSD fault
memory.
Control