Maintenance Factory - Johnson Controls FRICK QUANTUM HD Operation

Control panel
Hide thumbs Also See for FRICK QUANTUM HD:
Table of Contents

Advertisement

ACCESSING:
DESCRIPTION: Using this screen, the user can view up
to nine (9) pre-programmed maintenance schedules. This
screen is based upon the Maintenance Schedule that is
provided in the IOM manual for the specifi c compressor
package.
FACTORY
The above screen shows a row labeled as Oil
Analysis in the Task column. The next column
(Service Every) on the same row has a value
of 10000 Hrs. The last column (Next Service)
of this row has a value of 1000 Hrs. When the
compressor is running, this time value is being
clocked. After 1000 hours of compressor run
time, a message will be generated and placed
on the Event screen. This particular message
will read Maintenance -- Oil Analysis. This is to
notify the operator that it is time to have the Oil
checked. At this point, the operator should notify
the proper maintenance personnel that the ap-
propriate maintenance be performed. The user
should access the Event Screen on a regular ba-
sis (perhaps once per week) to review the infor-
mation provided there.
Once the message has been entered in the Event
Log, the values for the row will be automatically
updated, with new values as predetermined by
QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
SERVICE
Maintenance (Factory)
Maintenance
an internal programmed maintenance schedule,
based upon the type of compressor. The values
for the Next Service column are based upon the
Compressor Run Time hours (shown at the top
of this screen).
Modifying numerical values
When using the touchscreen, simply touch the
box that you wish to change, and enter the new
value into the setpoint box, then press [Enter].
When using the physical keypad, simply use the
[Tab] key to scroll down the lists, or the [Left
Arrow] key to scroll up the lists. When the box
that you wish to change is highlighted, you may
enter the new value using the numerical keys,
then press the [Enter] key to accept the value.
The following additional information is provided on
this screen:
Run Hours - The value shown here is the to-
tal number of hours that the compressor motor
has actually been in the running state. This value
can be reset (or changed to any value from 0 to
1,000,000 Hours) from the Panel screen.