ACCESSING:
DESCRIPTION: This screen is used to view and set basic
Ethernet operational values. NOTE: A valid internet ac-
count and connection must be available for this feature
to function.
IP ADDRESS
The following fi elds are provided:
[IP Address] - Four setpoint boxes are pro-
vided. The network administrator will enter
the numerical IP address for this specifi c
Quantum™ HD panel. This setpoint box will
be automatically assigned if the address
type is set to DHCP.
[Gateway Address] - Four setpoint boxes
are provided. The network or LAN admin-
istrator will enter the numerical Gateway
address. This setpoint box will be automati-
cally assigned if the address type is set to
DHCP.
[Subnet Mask] – Like IP addresses, a sub-
net mask contains four bytes (32 bits) and is
often written using the same "dotted-deci-
mal" notation. Subnet masks accompany an
IP address and the two values work togeth-
er. This setpoint box will be automatically
assigned if the address type is set to DHCP.
Applying the subnet mask to an IP address
splits the address into two parts, an extend-
QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
CONFIGURATION
Communications - Ethernet
Communications
Ethernet
ed network address and a host address. For
a subnet mask to be valid, its leftmost bits
must be set to '1'. Conversely, the rightmost
bits in a valid subnet mask must be set to
'0', not '1'. All valid subnet masks contain
two parts: the left side with all mask bits set
to '1' (the extended network portion) and
the right side with all bits set to '0' (the host
portion).
[Web Server Port] - One setpoint box is
provided. The network administrator will
enter the numerical address for this Web
port (80 is typical).
[Submit Changes] - Select this button after
changes have been made to the above set-
tings to submit them to the control program.
ETHERNET
The following fi elds are provided:
[ModBus TCP]
Disabled
Enabled
[Ethernet/IP]
Disabled
Enabled