PHD Vibration / Temperature - Motor Stator Temperature
ACCESSING:
DESCRIPTION: Use this screen to confi gure the Motor
Stator temperature(s). The following setpoint and selec-
tion boxes are provided:
MOTOR STATOR TEMPERATURE
Motor Stator Temperature
Disabled
Enabled
[High Warning] - If the Motor Stator tempera-
ture exceeds this setpoint for the amount of time
as set for the High Warning Delay, then a Warn-
ing is issued.
[High Warning Delay] - The time period as set
here will begin to time down if the Motor Stator
temperature exceeds that of the High Warning,
and remains above. When this delay times out, a
Warning will be issued.
[High Shutdown] - If the Motor Stator tempera-
ture exceeds this setpoint for the amount of time
as set for the High Shutdown Delay, then a Shut-
down will occur, and the compressor is stopped.
[High Shutdown Delay] - The time period as set
here will begin to time down if the Motor Stator
temperature exceeds that of the High Shutdown,
and remains above. When this delay times out,
QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
CONFIGURATION
PHD Vibration / Temperature
Motor Starter
a Shutdown will occur, and the compressor is
stopped.
[Low Limit] - If the Motor Stator temperature
falls below this setpoint, a Warning is issued.
[High Limit] - If the Motor Stator temperature
rises above this setpoint, a Warning is issued.
[Sensor Output] - The following selections are
provided:
0-5V
1-5V
4-20mA
ICTD
RTD
0-20mA
0-10V
2-10V
[I/O Board] - The following selections are pro-
vided:
None
Analog Bd 1
Analog Bd 2
[I/O Channel] - A setpoint entry box is provided
to select the analog board output channel that
you wish to use.