ACCESSING:
DESCRIPTION: Use these screens (Digital Aux. Output A
- J) to setup and control an Auxiliary Digital Output using
the signal from an Analog Input. The following descrip-
tions apply to all Digital Aux. Output pages.
The graphic below illustrates one scenario in which an
analog Temperature input is used to drive a digital output.
When the temperature exceeds the On When value of 75°,
the output will energize. It will remain in this state until
the analog input falls below the Off When value of 73°.
This state will persist until the input again exceeds the
On When value. The resulting temperature control would
resemble the following sine wave:
76°
75°
°
74
73°
Output is
de-energized
72°
QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
CONFIGURATION
Digital Auxiliaries - Digital Aux Outputs
Digital Auxiliaries
Output is
energized

Digital Aux Outputs

DIGITAL AUX. OUTPUT A - (Off or On status shown)
Analog Input
Capacity Slide Position
Volume Slide Position
Suction Pressure
Discharge Pressure
Compressor Oil Pressure
Main Oil Injection Pressure
Economizer Pressure
Filter Pressure
Intermediate Pressure
Balance Piston Pressure
System Discharge Pressure
Suction Temperature
Discharge Temperature
Compressor Oil Temperature
Oil Separator Temperature
Process/Brine Temperature Leaving
Process/Brine Temperature Entering
Remote Control Setpoint
Motor Current
RPM
User defi ned analog inputs #1 - #20
User defi ned analog inputs #12 - #20
Manifold Pressure
Remote Capacity Position
Compressor Vibration – Suction
Compressor Vibration – Discharge
Motor Vibration – Shaft Side
Motor Vibration – Opposite Shaft Side