Specification - Smartgen HMAT880 User Manual

Medium voltage bypass ats controller
Table of Contents

Advertisement

3 SPECIFICATION

Items
Working Voltage
Overall Consumption
AC Voltage Input (PT or PT
secondary side not used)
AC Frequency
AC Current
Aux. Output 1~4, 8, 10
Aux. Output 5~7, 9, 11~13
Digital Input 1~12
RS485 Interface
USB Interface
EMC Test Standard
Vibration
Shock
Bump
HMAT880 Medium Voltage Bypass ATS Controller User Manual
Table 3 – Performance Parameters
1. B+, B- terminal: DC12V/24V/48V;
2. PA, PN terminal: AC(90~305)V or DC110V/DC220V;
Either or both.
<6W (Standby mode: ≤2W)
AC system
3P4W (L-L)
(80~625)V
3P3W (L-L)
(80~625)V
1P2W (L-N)
(50~360)V
2P3W (L-L)
(80~625)V
Voltage Resolution: 1V
Accuracy: 1%
Rated: 50/60Hz
Range: 15Hz~75Hz
Resolution: 0.1Hz
Accuracy: 0.1Hz
Rated: 5A
Resolution: 0.1A
Accuracy: 1%
16A AC250V Volts free output
8A AC250V Volts free output
GND(B-) connected is active, low on threshold voltage ≤1.6VDC, max.
input voltage is 60VDC.
Isolated, half-duplex, 2400/4800/9600/19200bps baud rate can be set,
Modbus-RTU communication protocol, max. communication distance
can reach 1000m.
D-type USB interface
Meet GB/T14048.11-2016 and IEC/EN 60947-6-1
5Hz~8Hz: displacement=±7.5mm
8Hz~500Hz: a=±2g
IEC 60068-2-6
a=50g,
Pulse continuous time: 11ms,
Pulse waveform: half-sine, three consecutive shocks are applied in each
of the three mutually perpendicular directions, i.e. a total of 18 times.
IEC 60068-2-27
a=25g,
Pulse continuous time: 16ms,
Pulse waveform: half-sine,
IEC 60255-21-2
Contents