Use In Difficult Operating Conditions - YASKAWA SLIO CP 042-1IO00 Manual

Table of Contents

Advertisement

Basics and mounting
General data for the System SLIO > Use in difficult operating conditions
EMC
Emitted interference
Noise immunity
zone B
1) Due to the high-energetic single pulses with Surge an appropriate external protective circuit with lightning protection elements like conductors for lightning and overvoltage is
necessary.
2.14.1

Use in difficult operating conditions

44
Standard
EN 61000-6-4
EN 61000-6-2
EN 61000-4-2
EN 61000-4-3
EN 61000-4-6
EN 61000-4-4
EN 61000-4-5
Without additional protective measures, the products must not be used in
locations with difficult operating conditions; e.g. due to:
dust generation
chemically active substances (corrosive vapors or gases)
strong electric or magnetic fields
Comment
Class A (Industrial area)
Industrial area
ESD
8kV at air discharge (degree of severity 3),
4kV at contact discharge (degree of severity 2)
HF field immunity (casing)
80MHz ... 1000MHz, 10V/m, 80% AM (1kHz)
1.4GHz ... 2.0GHz, 3V/m, 80% AM (1kHz)
2GHz ... 2.7GHz, 1V/m, 80% AM (1kHz)
HF conducted
150kHz ... 80MHz, 10V, 80% AM (1kHz)
Burst, degree of severity 3
Surge, degree of severity 3
HB300 | CP | 042-1IO00 | en | 22-42
System SLIO
1

Advertisement

Table of Contents
loading

Table of Contents