System SLIO

4.6 Firmware update

Proceeding
HB300 | CP | 042-1IO00 | en | 22-42
CAUTION!
When installing a new firmware you have to be extremely careful. In
certain circumstances, your CP 042 IO-Link may become unusable if,
for example, the power supply is interrupted during transmission or
the firmware file is faulty. In this case, please call the Yaskawa hot-
line!
The update deletes the port configurations saved in the IO-Link
master and resets the parameters to their default values.
n
You can only apply a firmware update via the IO-Link Manager.
n
You can find current firmware versions in the 'Download Center' of
www.yaskawa.eu.com.
For example, the following file is required for the firmware update of the 042-1IO00 for
hardware revision 01:
Bx000808.bin
n
1.
Go to the 'Download Center' of www.yaskawa.eu.com.
2.
Download the corresponding zip file for your IO-Link master to your PC at
'Firmware' , by stating the order number.
3.
Extract the zip file into your working directory.
4.
Switch on the power supply for your system.
5.
Open the IO-Link Manager and establish an online connection to your IO-Link
master via the head module..
6.
Select the corresponding IO-Link master in 'Topology' .
7.
Navigate to the firmware update dialog via 'Master Control
è Advanced Master Control è General'.
To identify the IO-Link master, you can localize it on the System
SLIO bus. To do this, enter a period of time in seconds at "Locate
Master ..." and click on [ACTIVATE]. This starts the localisation with
device-specific blinking behavior at the corresponding IO-Link
master for the set period of time.
8.
At 'System Management' navigate with
tory.
9.
Start the firmware update with [Update].
ð During the firmware update, the LEDs C1, F3 and C2, F4 are blinking alter-
nately. After the update, the IO-Link master is restarted without configuration
with default parameters.
If only the LEDs C1 and C2 are blinking alternately, an error has
occurred, the IO-Link master is still in Bootloader Mode and
indicates this at 'TOPOLOGY' . Check that the firmware file
matches your IO-Link master and run the update again. If the
error persists, please contact the Yaskawa hotline!
your firmware file in the working direc-
. . .
Deployment
Firmware update
61