Nortel DMS-100 Series Maintenance Manual page 247

Remote line concentrating module with extended distance capability
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

Replacing an NT2X90 card in an RMM
At your current location
1
Proceed only if this card replacement procedure sent you to a step in a
maintenance procedure. If you use the procedure to verify or accept cards you
may proceed. You may proceed if your maintenance support group sent you to
this procedure.
2
Obtain a replacement card. Make sure that the replacement card has the same
product equipment code (PEC) including suffix as the card you remove.
At the MAP display
3
To access the TTP level of the MAP display and post the trunk circuits that
associate with the card you replace, type:
>MAPCI;MTC;TRKS;TTP;POST P RMM rmm_no ckt_no ckt_no
and press the Enter key.
where
rmm_no
is the number of the RMM that contains the card you replaced
ckt_no
is the number of the first circuit that associates with the defective
card
ckt_no
is the number of the last circuit that associates with the defective
card
Example of a MAP response:
LAST CIRCUIT = 27
POST CKT IDLED
SHORT CLLI IS:
OK, CLLI POSTED
POST
DELQ
TTP 6–006
CKT TYPE
PM NO.
OG
RMM 0 0
4
To make sure you pull the correct card from the correct card slot,
>CKTLOC
and press the Enter key.
5
To busy the trunk circuits that associate with the defective card you replace,
type:
>BSY ALL
and press the Enter key.
RLCM-EDC card replacement procedures 6-59
MONTALK
BUSY Q
COM LANG
MONTALK
21
DMS-100 Family Maintenance Manual ABSK007
NT2X90
in RMM
(continued)
DIG
STA S R DOT TE R
LO
P_IDL
type: