Nortel DMS-100 Series Maintenance Manual page 224

Remote line concentrating module with extended distance capability
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

6-36 RLCM-EDC card replacement procedures
NT2X11
NT2X11
in RMM
in RMM
(end)
(continued)
At the MAP display
5
6
7
8
9
10
297-8381-550 Standard 02.02 April 1999
To test the new NT2X11 card, type
>TST
and press the Enter key.
If TST
passed
failed
To return to service the circuits busied in step 3, type
>RTS
and press the Enter key.
If RTS
passed
failed
To send the damaged cards for repair follow the local procedures.
Record the items that follow in office records:
date the replaced card
serial number of the card
indications that prompted replacement of the card
Go to step 10.
To replace this card you can obtain additional help. For additional help contact
the personnel responsible for next level of support.
You have completed this procedure.