Nortel DMS-100 Series Maintenance Manual page 192

Remote line concentrating module with extended distance capability
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

6-4 RLCM-EDC card replacement procedures
NT0X10
in RMM
(continued)
Replacing an NT0X10 in RMM
At your current location
1
At the MAP display
2
At the RMM shelf
3
297-8381-550 Standard 02.02 April 1999
Obtain a replacement card. Make sure that the replacement card has the same
PEC, PEC suffix, as the card removed.
To access the Trunk Test Position (TTP) level of the MAP terminal and post the
SC associated with the defective card, type:
>MAPCI;MTC;TRKS;TTP;POST P RMM rmm_no ckt_no
and press the Enter key.
where
rmm_no
is the number of the RMM with the defective NT0X10 card
ckt_no
is the number of the first scan point of the seven SC
points on this card.
Example of a MAP display response:
LAST CIRCUIT = 14
POST CKT IDLED
SHORT CLLI IS:
OK, CLLI POSTED
POST
13
DELQ
TTP 6–006
CKT TYPE
PM NO.
OG TESTEQ
RMM 0 0
WARNING
Static electricity damage
Wear a wrist strap that connects to the wrist-strap
grounding point of a frame supervisory panel (FSP) to
handle circuit cards. The wrist strap protects the cards
against static electricity damage.
To replace the NT0X10 card use the procedure, Replacing a card. When you
complete the procedure, return to this point or go to step 7.
1146
BUSY Q
COM LANG
OAUSC
0
DIG
STA S R DOT TE R
IDL