Replacing an NT2X06 in an RMM
At your current location
1
Obtain a replacement card. Ensure that the replacement card has the same
product equipment code (PEC), including suffix, as the card to be removed.
2
If you were directed to this procedure from the Alarm Clearing Procedures , go
to step 8. Otherwise, continue with step 3.
At the MAP terminal
3
Access the TTP level of the MAP and post the RMM that contains the card to
be replaced by typing
>MAPCI;MTC;TRKS;TTP;POST P RMM rmm_no
and pressing the Enter key.
where
rmm_no
is the number of the RMM shelf in which the card is to be replaced
Example of a MAP response:
LAST CIRCUIT = 27
POST CKT IDLED
SHORT CLLI IS:
OK, CLLI POSTED
POST
20
DELQ
TTP 6–006
CKT TYPE
PM NO.
OG
RMM 0 0
4
Check the status of the RMM.
If RMM status is
MB, PMB, RMB
other
5
Busy the trunks that are associated with the RMM to be busied by typing
>BSY ALL
and pressing the Enter key.
RLCM-EDC card replacement procedures 6-19
MTU
BUSY Q
COM LANG
MTU 20
DMS-100 Family Maintenance Manual ABSK007
in RMM
(continued)
DIG
STA S R DOT TE R
LO
P_IDL
Do
step 8
step 5
NT2X06