Mounting Sequence - WAGO 750 Manual

16do 24vdc 0.5 a, low-side switching 16-channel digital output module 24 vdc; low-side switching
Table of Contents

Advertisement

30
Mounting
5.1

Mounting Sequence

Fieldbus couplers, controllers and I/O modules of the WAGO I/O System 750 are
snapped directly on a carrier rail in accordance with the European standard EN
60175 (DIN 35).
The reliable positioning and connection is made using a tongue and groove
system. Due to the automatic locking, the individual devices are securely seated
on the rail after installation.
Starting with the fieldbus coupler or controller, the I/O modules are mounted
adjacent to each other according to the project design. Errors in the design of the
node in terms of the potential groups (connection via the power contacts) are
recognized, as the I/O modules with power contacts (blade contacts) cannot be
linked to I/O modules with fewer power contacts.
Pos : 69.8 /Serie 750 (WAGO I/O SYSTEM)/Wic htige Erläuterungen (al te Str uktur)/Sic herheits- und sonstige Hinweis e/Achtung/Ac htung: I/O-Module nur in vorg esehener R eihenfolge stec ken! @ 6\mod_1256194177073_21.doc x @ 43429 @ @ 1
Insert I/O modules only from the proper direction!
All I/O modules feature grooves for power jumper contacts on the right side. For
some I/O modules, the grooves are closed on the top. Therefore, I/O modules
featuring a power jumper contact on the left side cannot be snapped from the
top. This mechanical coding helps to avoid configuration errors, which may
destroy the I/O modules. Therefore, insert I/O modules only from the right and
from the top.
Pos : 69.9 /Serie 750 (WAGO I/O SYSTEM)/Wic htige Erläuterungen (al te Str uktur)/Sic herheits- und sonstige Hinweis e/Hinweis/Hi nweis: Busabsc hlus s nicht vergess en! @ 6\mod_1256194225557_21.doc x @ 43432 @ @ 1
Don't forget the bus end module!
Always plug a bus end module (e.g. 750-600) onto the end of the fieldbus node!
You must always use a bus end module at all fieldbus nodes with WAGO I/O
System 750 fieldbus couplers or controllers to guarantee proper data transfer.
Pos : 69.10 /Alle Serien (Allgemeine M odul e)/Übersc hriften/Ebene 2/Ger äte einfügen und entfernen - Ü bersc hrift 2 @ 3\mod_1231768483250_21.doc x @ 25950 @ 2 @ 1