Table 80: Mounting Hole Locations for Installing a Chassis in an Open-Frame Rack
Hole
Distance Above U Division
104
60.38 in. (153.4 cm)
95
55.13 in. (140.0 cm)
86
49.88 in. (126.7 cm)
77
44.63 in. (113.3 cm)
68
39.38 in. (100.0 cm)
59
34.13 in. (86.7 cm)
50
28.88 in. (73.3 cm)
41
23.63 in. (60.0 cm)
32
18.38 in. (46.7 cm)
23
13.13 in. (33.3 cm)
Installing the Open-Frame Rack Mounting Shelf
Before mounting the chassis in an open-frame rack, you must first install the open-frame rack mounting
shelf.
To install the open-frame rack mounting shelf (see
1. On the rear of each rack rail, partially insert a mounting screw into the highest hole specified in
3
for the open-frame rack mounting shelf.
2. Install the open-frame rack mounting shelf on the rack. Hang the shelf over the mounting screws by
using the keyhole slots located near the top of the shelf flanges.
3. Partially insert screws into the open holes in the flanges of the open-frame rack mounting shelf.
Figure 82 on page
213):
34.50 U
31.50 U
28.50 U
25.50 U
22.50 U
19.50 U
16.50 U
13.50 U
10.50 U
7.50 U
Table
212