Ground cabling

The frame ground cabling and the logic return cabling are described and
illustrated in this subsection.

Frame Ground (FGND) cabling

The Frame Ground (FGND) cabling connects a #6 AWG wire between the
ground source, typically the Frame Ground Equalizer (FGE) or Single Point
Ground (SPG), and the ground lug on the rear of the first IPEC. Ground lugs
from each pedestal are connected together in a daisy-chain arrangement using
Meridian SuperNode MSL-100 Intelligent Peripheral Equipment (IPE) Reference Manual MSL14
Card Slot
Pins
13
37, 38, 39, 40
15
33, 34, 35, 36
15
37, 38, 39, 40
13
54, 55, 56, 57
13
58, 59, 60, 61
15
54, 55, 56, 57
15
58, 59, 60, 61
13
62, 63, 64, 65
13
66, 67, 68, 69
15
62, 63, 64, 65
15
66, 67, 68, 69
13
70, 71, 72, 73
13
74, 75, 76, 77
15
70, 71, 72, 73
15
74, 75, 76, 77
13
78, 79, 80, 81
13
82, 83, 84, 85
15
78, 79, 80, 81
15
82, 83, 84, 85
Cabling specifications 4-21
A, B
C, D
C, D
A, B
A, B
C, D
C, D
A, B
A, B
C, D
C, D
A, B
A, B
C, D
C, D
A, B
A, B
C, D
C, D

Advertisement

Table of Contents
loading

This manual is also suitable for:

Meridian sl-100

Table of Contents